IDEAL imax plus F80 Installation And Servicing page 26

Table of Contents

Advertisement

29 PARAMETER MODE CONT'D
Press
Display
A. 0 1
B. 2 0
C. 2 0
D. 2 0
E. 2 0
F. 2 0
G. 2 0
H. 2 0
J. 2 0
L. 2 0
N. 2 0
26
INSTALLATION
Description
1st Digit - CH type
0x = Timer/Thermostat with optional weather compensation
1x = Outside Sensor with Night Time Set back
2x = BMS 0-10V Control
2nd Digit - DHW type
x0 = 3-way valve normally open to CH system
x1 = DHW pump
x2 = 3-way valve normally open to DHW tank
DHW set value increase (degC)
Temperature added to parameter 1 (see Frame 28) for boiler flow
temperature required to satisfy DHW demand
Maximum fan speed CH (hundreds rpm)
Maximum fan speed DHW (hundreds rpm)
Minimum fan speed (hundreds rpm)
Ignition fan speed (% of parameter C)
Flow temperature set point at 0V (degC)
When using 0-10V BMS
Flow temperature set point at 10V (degC)
When using 0-10V BMS
1st digit - Number of module lockouts required to close alarm contacts
2nd digit - DHW pump overrun time (30 second increments)
DHW hysteresis (degC)
1st digit - Burner System
0x = Ideal normal setup
2nd digit - Number of Modules
Lower
Upper
Factory
Limit
Limit
Setting
01
5
25
20
DO
DO
NOT
NOT
58
ADJUST
ADJUST
DO
DO
NOT
NOT
58
ADJUST
ADJUST
DO
DO
NOT
NOT
22
ADJUST
ADJUST
DO
DO
NOT
NOT
75
ADJUST
ADJUST
0
50
30
50
90
80
1x
7x
2x to 7x
x0
x9
x1
5
14
05
DO
DO
0x
NOT
NOT
ADJUST
ADJUST
x2 to x7
-
Installation & Servicing