Installation; Parameter Mode; Parameters Accessible To User - IDEAL imax plus F80 Installation And Servicing

Table of Contents

Advertisement

28 PARAMETER MODE

By pressing the mode key once, PARA mode (abbreviation for
parameter) is displayed. In this mode it is possible to change
the settings of the boiler control module.
Press
Display
P A R A

Parameters accessible to user

Press
Display
1. 6 0
2. 0 1
3. 8 0
Parameters accessible to trained installers and service engineers only, after entering service code.
Press
Display
4. 2 0
5. 2 0
6. 2 0
7. 2 0
8. 0 0
9. 2 0
-
Installation & Servicing

INSTALLATION

Description
DHW Storage Temperature Setpoint (degC)
CH and DHW Options
00 = CH & DHW are both off
01 = CH is on, DHW is off
02 = CH is on, DHW is off, System pump runs continuously
11 = CH & DHW are both on
12 = CH & DHW are both on, System pump runs continuously
Maximum CH Flow Temperature Setpoint (degC)
Description
Flow Temperature Minimum Design Setpoint (degC)
see Frame 34 for guidance
Outside Temperature Minimum Design Value (degC)
see Frame 34 for guidance
Minimum Flow Temperature Blocking Setpoint (degC)
see Frame 34 for guidance
Night time Setback Parallel Shift (degC)
see Frame 35 for guidance
1st digit - Outside Temperature Correction (degC)
see Frame 34 or 35
2nd Digit - CH hysteresis (degC)
CH Pump Overrun Time (minutes)
Lower
Upper
Factory
Limit
Limit
Setting
40
65
60
-
-
11
30
90
80
Lower
Upper
Factory
Limit
Limit
Setting
15
60
20
-20
10
-10
15
30
25
00
40
10
-5x
5x
09
x0
x9
3
99
05
25