Mixing Header - IDEAL imax plus F80 Installation And Servicing

Table of Contents

Advertisement

2

MIXING HEADER

For the correct operation of the boiler, the use of a mixing
header is advisable because it provides:
-
separation and collection of circuit dirt
-
good air venting
-
separation of the two hydraulic circulation circuits
PRIMARY
F
I
L
T
E
R
Use the Table below as a guide for sizing a suitable mixing header.
Model
80 kW
120 kW
160 kW
200-240-280 kW
8
FLOW
BOILER
g
CIRCUIT
RETURN
D
BF BR
HF HR
mm
DN
DN
100
50
50
150
65
65
200
80
80
200
100
100
GENERAL
The use of a mixing header means that compensating controls
can be used to operate mixing valves on a variable temperature
circuit, without affecting the water flow rate through the boiler.
D
1
/
"
2
HF
g
HR
1
/
"
2
a
b
mm
mm
mm
200
300
1,000
200
300
1,000
200
300
1,000
200
300
1,000
e
FLOW
SECONDARY
HEATING
c
CIRCUIT
h
RETURN
b
a
c
e
h
mm
mm
150
1,650
150
1,650
150
1,650
150
1,650
-
Installation & Servicing
g
mm
200
200
200
200