10.0 Fluing Options

Please note that excessive resistance within the flue and combustion air supply systems will lead to a
reduction in the output of the appliance and induce operational faults.
80/125mm Concentric Flue Components (Pa Resistances)
Wall Terminal
Vertical Terminal
955mm Flue Extension
500mm Flue Extension
255mm Flue Extension
87º Bend
45º Bend
30º Bend
80mmØ PPS Flue Components (Pa Resistances)
Exhaust Pipe Terminal
Air Pipe Terminal
955mm Flue Extension
500mm Flue Extension
255mm Flue Extension
87º Bend
45º Bend
30º Bend
When flues are installed with horizontal sections/portions a 3
maintained. This will not only ensure condensate removal preventing premature seal failure, but also
prevent nuisances dripping from the wall terminal.
10.01 Replacing a MicroMat EC 60-75 with a ProCon 77 complete with Flue Adapter. (DN80/125mm)
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR
Telephone 08456 448802 Fax 08456 448803 Email
© MHG Heating Ltd
16
4.0
4.0
2.5
1.25
1.0
2.5
1.25
1.00
1.0
2.0
1.5
0.75
0.5
1.5
0.75
0.5
0
MicroMat EC Flue adapter part number 96.36400-7020
info@mhgheating.co.uk
010711
27
5.0
5.0
4.0
2.0
1.5
4.0
2.0
1.5
2.5
4.0
3.0
1.5
1.0
3.0
1.5
1.0
fall back to the boiler must be
Web www.mhgheating.co.uk
47
75 & 77
8.0
16.0
8.0
16.0
6.0
12.0
3.0
6.0
2.0
4.0
6.0
12.0
3.0
6.0
2.0
4.5
4.0
8.0
7.0
15.0
5.0
9.0
2.25
4.5
2.0
3.75
5.0
9.0
2.25
4.5
1.75
3.5
36