Charging; Refrigerant Charge; Hfc134A Service Information; Health, Safety, And Handling - Viking VCBF036RSS Service Manual

Bottom mount freezer
Hide thumbs Also See for VCBF036RSS:
Table of Contents

Advertisement

Service Procedure

Charging

NOTE: Do not use captured or recycled refrigerant in
units. Captured or recycled refrigerant voids any
warranty.
NOTE: Charge system with exact amount of refrigerant.
Refer to unit serial plate for correct refrigerant
charge. Inaccurately charged system will cause
future problems.
To charge system:
Close valves "A" to vacuum pump and "C" to vacuum
gauge and "E" to low side manifold gauge.
9. Set scale on dial-a-charge cylinder for
corresponding HFC134a pressure reading.
10. Open valve "F" to charging cylinder and let exact
amount of refrigerant flow from cylinder into system.
Close valve.
Low side gauge pressure should rise shortly after
opening charging cylinder valve as system pressure
equalizes through capillary tube.
If pressure does not equalize, a restriction typically
exists at capillary/drier braze joint.
11. If pressure equalizes, open valve "E" to low side
manifold gauge and pinch off high side drier process
tube.
12. Start compressor and draw remaining refrigerant
from charging hoses and manifold into compressor
through compressor process tube.
13. To check high side pinch-off drier process tube.
Close valve "D" to high side gauge. If high side
pressure rises, repeat high side pinch-off and open
valve "D". Repeat until high side pinch-off does not
leak.
14. Pinch-off compressor process tube and remove
charging hose. Braze stub closed while compressor
is operating.
15. Disconnect power. Remove charging hose and
braze high side drier process tube closed.
16. Recheck for refrigerant leaks.
34

Refrigerant Charge

Refrigerant charge in all capillary tube systems is critical
and exact amount is required for proper performance.
Factory charges are shown on serial plate.
NOTE: Do not use refrigerant other than shown on
serial plate.

HFC134a Service Information

HFC134a is alternative refrigerant for CFC12.
HFC134a has an ozone depletion potential (ODP) factor
of 0.0 and a global warming potential (GWP) factor of
0.27. HFC134a is not flammable and has acceptable
toxicity levels. HFC134a is not interchangeable with
CFC12. There are significant differences between
HFC134a and CFC12 which must be considered when
handling and processing refrigeration system.

Health, Safety, and Handling

Health, safety and handling considerations for HFC134A
are virtually no different than those for CFC12.
Health, Safety, and
Handling
Allowable overall
exposure limit
Vapor exposure to skin
Liquid exposure to skin
Vapor exposure to eye
Liquid exposure to eye
Above minimum
Can cause Asphyxiation,
exposure limit
Safety and handling
Spill management
Fire explosion hazards
if heated due to resulting
Disposal procedures
CFC12
HFC134a
1,000 ppm
Same
No effect
Same
Can cause frostbite
Same
Very slight eye irritant
Same
Can cause frostbite
Same
Same
Tachycardia, and Cardia
Arrhythmias
Wear appropriate skin
Same
and eye protection. Use
with adequate
ventilation.
Remove or extinguish
Same
ignition or combustion
sources. Evacuate or
ventilate area.
May decompose if
Same
contact with flames and
heating elements.
Container may explode
pressure rise.
Combustion products
are toxic.
Recycle or reclaim.
Same