C. Termination Requirements
Install a cap approved and listed for this fireplace system.
Locate cap where it will not become plugged by snow or other materials.
Locate cap away from trees or other structures.
The bottom of the termination cap must be at least 3 ft (.91 m) above the roof AND at least 2 ft (.61 m) above any portion
of roof within 10 ft (3.05 m).
The distance required between caps is shown below.
Slanted Roofs
Chimney must
extend 3 ft (.9 m)
above the roof
Flat Roofs
Chimney must
extend 3 ft (.9 m)
above the roof
Multiple Chimney Locations
6 in. (minimum) up to 20 in.
152 mm/508 mm
20 in. and over
Figure 4.3
Multiple Chimney Locations
VCG Biltmore Series • SB100 • 4013-303 Installers Manual • Rev A • 02/19/15
A
B
18 in. minimum
457 mm
0 in. minimum
Chimney must extend 2 ft (.6 m)
above any portion of the roof or
adjacent structures within
10 ft (3 m) of the chimney
Chimney must extend 2 ft (.6 m)
above any portion of the roof or
adjacent structures within
10 ft (3 m) of the chimney
Gas, Wood or Fuel Oil
Termination Cap
B
Gas
Termination
Cap **
*
If using decorative cap cover(s), this distance may need to be
increased. Refer to the installation instructions supplied with the
decorative cap cover.
**
In a staggered installation with both gas and wood terminations, the
wood termination cap must be higher than the gas termination cap.
Wood
Minimum
(See
A *
illustration
above)
19