Commissioning
Connected extra sensors
Yes must apply for T5 acknowledged when room sensor T5 is used.
Connection capacity
Important and must be changed
State total output: Setting of total connected output on the additional heat.
The factory setting is 13.5 kW. Change this to 4.5 kW.
Compressor mode, output limitation: Setting permitted output when the
compressor is in operation. The factory setting is 50% of the setting in State
total output, that is 6,75 kW. Min = 0.25 kW, max = the value set in State
total output. Change this to 4.5 kW.
Additional heat only, output limitation: Setting permitted output when the
compressor is not in operation. Factory setting is the setting in State total
output, that is 13,5 kW. Min = 0.25 kW, max = the value set in State total
output.

Manual operation

Make a check of all the functions before you commission the heating
installation. You can manually start and stop the pumps and valves from the
menu Manual Operation. Select Yes to activate.
NOTE! The function is deactivated by selecting No in Manual Operation.
Additional heat options
Additional heat only blocks the start of compressor and fan. Heating and
hot water is supplied via the additional heat.
Block additional heat blocks the additional heat function, but not during
alarm mode, hot water peak, extra hot water or operation with additional
heat only.
NOTE! Normally this is not recommended.
Language
This allows you to change the language to one other than that selected
when the heat pump was fi rst started. The selected language automatically
becomes the factory setting, that is, is not changed by Return to factory
settings.
Correct sensor
All sensors can be corrected here. The correction value is stated directly
in °C. Normally one should avoid correcting a sensor. The value that
is given without correction is most often the correct one. Correction of
maximum 5ºC up or down is possible.
For single phase units, change the con-
nection capacity which speeds up the
additional electric heater ramp up time.
32