Section 6: Mobile Home - Quadra-Fire CB1200M-MBK Installation And Operation Maintenance

Classic bay 1200 pellet stove
Hide thumbs Also See for CB1200M-MBK:
Table of Contents

Advertisement

CB 1200 Pellet Stove
6
Mobile Home
A. Mobile Home Installation
You must use a Quadra-Fire Outside Air Kit
for installation in a mobile home.
1.
An outside air inlet must be provided for the combustion
air and must remain clear of leaves, debris, ice and/or
snow. It must be unrestricted while the appliance is
in use to prevent room air starvation which causes
smoke spillage. Smoke spillage can also set off smoke
alarms.
2.
The combustion air duct system must be made of
metal. It must permit zero clearance to combustible
construction and prevent material from dropping into
the inlet or into the area beneath the dwelling and
contain a rodent screen.
3.
The appliance must be secured to the mobile home
structure by bolting it to the fl oor (using lag bolts) in two
places. Use the same holes that secured the appliance
to the shipping pallet.
4.
The appliance must be grounded with #8 solid copper
grounding wire or equivalent, terminated at each end
with an NEC approved grounding device.
5.
Refer to Clearances to Combustibles and fl oor pro-
tection requirements on pages 9 & 10 for listings to
combustibles and appropriate chimney systems.
6.
Use silicone to create an effective vapor barrier at
the location where the chimney or other component
penetrates to the exterior of the structure.
7.
Follow the chimney manufacturer's instructions when
installing the vent system for use in a mobile home.
8.
Installation shall be in accordance with the Manufactur-
ers Home & Safety Standard (HUD) CFR 3280, Part
24.
WARNING
Installation must comply with Manufactured Home and
Safety Standard (HUD), CFR 3280, Part 24.
WARNING
NEVER INSTALL IN A SLEEPING ROOM.
Page 18
THE STRUCTURAL INTEGRITY OF THE MANUFAC-
TURED HOME FLOOR, WALL AND CEILING/ROOF MUST
BE MAINTAINED.
Do NOT cut through:
• Floor joist, wall, studs or ceiling trusses.
• Any supporting material that would affect the structural
integrity.
Never draw outside combustion air from:
Wall, fl oor or ceiling cavity
Enclosed space such as an attic or garage
Storm Collar
Joist Shield/Firestop
Figure 18.1
7014-179K
CAUTION
CAUTION
Spark Arestor Ca
Roof Flashing
Double Wall
Connector Pipe
R
May 6, 2015