Vertical; Vertical - Internal - Quadra-Fire CB1200M-MBK Installation And Operation Maintenance

Classic bay 1200 pellet stove
Hide thumbs Also See for CB1200M-MBK:
Table of Contents

Advertisement

CB 1200 Pellet Stove
C. Vertical into Existing Class A Chimney
Flashing
Firestop
Ceiling Support
6 in.
(152mm)
Min.
Non-combustible Hearth Pad
Figure 16.1
D. Through The Wall & Vertical - External
2 in. (51mm) Minimum
6 in. (152mm)
Minimum
Non-combustible Hearth Pad
Figure 16.2
Page 16
Rain Cap
24 in. (610mm)
minimum
Class A Chimney
Connector Adapter
3 in. (76mm)
Min.
Top Vent Kit
Clean-out
Cover
Rain Cap
24 in. (610mm)
Flashing
Minimum
Support Bracket
every 60 in. (1524mm)
Wall Thimble
Tee
Clean-out Cover
We recommend a minimum of 60 in. (1.5m) vertical,
however above the eve is preferred.
Both installations are approved for mobile home instal-
lations. Must use 3 or 4 inch (76 to 102mm) "L" or
"PL" Listed pellet venting or listed double wall pipe and
Quadra-Fire outside air kit in mobile homes. Single
wall pipe is approved for residential installations only.
E. Vertical - Internal - Typical Installation
Flashing
Firestop
6 in.
(152mm)
Min.
Non-combustible Hearth Pad
Figure 16.3
7014-179K
R
Rain Cap
24 in.
(610mm)
Minimum
3 in. (76mm) Min.
3 in. to 3 in.
(76-76mm)
Top Vent Kit
Clean-out Cover
May 6, 2015