Dell PowerEdge R930 Owner's Manual page 175

Hide thumbs Also See for PowerEdge R930:
Table of Contents

Advertisement

NOTE: Applies to data center environments
only. Air filtration requirements do not apply
to IT equipment designed to be used
outside a data center, in environments such
as an office or factory floor.
Conductive Dust
NOTE: Applies to data center and non-data
center environments.
Corrosive Dust
NOTE: Applies to data center and non-data
center environments.
Gaseous Contamination
NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Copper Coupon Corrosion Rate
Silver Coupon Corrosion Rate
Air must be free of conductive dust, zinc whiskers,
or other conductive particles.
Air must be free of corrosive dust.
Residual dust present in the air must have a
deliquescent point less than 60% relative
humidity.
<300 Å/month per Class G1 as defined by ANSI/
ISA71.04-1985.
<200 Å/month as defined by AHSRAE TC9.9.
175