Insert Size Requirements; Insert Placement Requirements; Hearth Requirements - Lopi Answer Wood Stove Owner's Manual

Lopi answer wood stove owner's manual
Table of Contents

Advertisement

Insert Installation
18
Insert Size Requirements (see Illustration below)
j
i

Insert Placement Requirements

The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" of the front of the insert
Insert and hearth must be installed on a level, secure floor
The minimum clearances, facing, and hearth requirements in the illustration below must be met
(follow the clearances for the type of fireplace being used - either masonry or zero-clearance).
Side
Wall
k
p
q

Hearth Requirements

Must extend 16" in front of the insert and 8" on both sides (total of 19" deep by 39 5/8" wide)
Must be non-combustible 1/4" thick insulating board with a thermal conductivity of K=0.72
Travis Industries
Minimum Fireplace Size
h
b
a
d
c
e
g
f
n
m
l
x
o
(for qualified installers only)
a
Height (front)
b
Height (rear)
c
Width (front)
d
Width (rear)
e
Depth
f
Hearth Depth*
Hearth Width
g
Facing Width
h
i
Facing Height
j
Mantel Height
* This is the distance the insert protrudes from
the fireplace opening plus the required 16" of
hearth extension.
Minimum Clearances
k
Sidewall to Insert
l
Side Facing
m
Top Facing
n
Mantel to Insert
o
Hearth (Front)*
p
Hearth (Side)
q
Front of Insert
x
Extension onto Hearth
* Does not include the distance the insert
extends onto the hearth (dimension "x").
93508131
Masonry
Z.C. (Metal)
Fireplace
Fireplace
20-3/4"
20-3/4"
20-3/4"
20-3/4"
23-5/8"
25-5/8"
23-5/8"
25-5/8"
13-1/2"
14-1/2"
19"
19"
39-5/8"
39-5/8"
42-5/8"
47-5/8"
32"
32"
35-1/2"
44"
Masonry
ZC (Metal)
Fireplace
Fireplace
13"
30"
9-1/2"
12"
12"
12"
15-1/2"
24"
16"
16"
8"
8"
36"
36"
3"
3"
4 020327