Fireplace Insert Installation

Insert Placement Requirements

The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" of the front of the insert (Figure 17 "q").
Insert and hearth must be installed on a level, secure floor
The minimum clearances, facing, and hearth requirements in Figure 17 must be met. Follow the
clearances for the type of fireplace being used – (masonry or zero-clearance-metal).
Side
Wall
k
l
p
q

Hearth Requirements

Must extend 16" in front of the insert and 8" on both sides (min. 19" deep by 39-5/8" wide)
Must be non-combustible and at least .018" thick (26 gauge)

Masonry Fireplace Requirements

Chimney must have a clay tile liner or a stainless steel liner (positive connection).
Entire fireplace, including chimney, must be clean and undamaged. Any damage must be repaired
prior to installation of the insert.
Chimney height: 15' minimum; 33' maximum.
Entire fireplace, including chimney, must meet local building requirements.
© Travis Industries
n
m
x
o
100-01166
(for qualified installers only)
Minimum
Masonry
Clearances
Fireplace
k Sidewall
13"
331mm
l Side Facing
9.5"
(non-
242mm
combustible)
m Top Facing
12"
(non-
305mm
combustible)
n Mantel
15.5"
(combustible)
394mm
o Front Hearth
16"
(does not
407mm (US)
include insert
- - - - - - - - - - -
extension "x")
18"
458mm
(Canada)
8"
p Side Hearth
204mm
36"
q Front of Insert
915mm
x Extension Onto
3"
Hearth
77mm
Z.C. (Metal)
Fireplace
30"
762mm
12"
305mm
12"
305mm
24"
610mm
16"
407mm (US)
- - - - - - - - - - -
18"
458mm
(Canada)
8"
204mm
36"
915mm
3"
77mm
Figure 17
4040907