2)
In the case of construction elements that only border small areas of
the cassette (wall, floor or ceiling coverings), it is recommended that
you maintain a distance of 10 mm.
Wooden beams must not be fitted in the fireplace's thermal radiation field.
Any wooden beams above a fireplace must be completely ventilated on all
sides by a minimum of 1 cm. Directly fixing them to thermal bridges is not
allowed.
Heat insulation materials are only required when the adjacent construction
components of the building / fireplace location etc. need to be protected
against "high" temperatures. This is the case for combustible and load-
bearing construction components.
The insulation thicknesses listed are based on the reference insulation
material rock wool according to AGI-Q 132. Silicon-based insulation material
can also be used with the relevant building approvals. These materials enable
a significant reduction in the insulation thickness (e.g. Silka type: 250 KM)
2.13.1
Fireplace
cassette
XS 500
S 600
M 700
L 800
XL 900
Air intake openings and air circulation openings must have the following
dimensions. See table. At least 50% of all of the indicated openings must not
be closable.
Fireplace cassette
Air circulation
openings in cm²
Air intake openings
in cm²
2.12 Wooden beams
2.13 Heat insulation material
Heat insulation thicknesses (rock wool accord-
ing to AGI Q 132)
Installation
Flooring
0 mm
0 mm
0 mm
0 mm
0 mm
XS 500
220
450
framework PAGE - 22 -
wall
50 mm
140 mm
140 mm
140 mm
140 mm
S 600
M 700
240
290
Adjacent
Ceiling
50 mm
100 mm
100 mm
100 mm
100 mm
L 800
400
640
450
730
wall
60 mm
80 mm
80 mm
80 mm
80 mm
XL 900
880
960