Note: If vent pipe passes through any occupied areas above first floor,
including storage spaces and closets, you must enclose pipe. You may
frame and sheetrock enclosure with standard construction material. Make
sure and meet the minimum allowable clearances to combustibles. Do not
fill any required air spaces with insulation.
If area above is an attic or insulated area,
install firestop above framed hole.
If area above is a living space, install
firestop below framed hole.
Figure 18 - Installing Firestop
Vertical Termination Configurations
Figures 19 and 20, show the configurations for vertical termination.
Vertical
Venting
V = 40' max.
Note: Install
Restrictor into
Inner Collar of
Fireplace as
Shown
Figure 19 - Vertical Venting Configuration
14
VENTING INSTALLATION Continued
Figure 20 - Vertical Venting Configuration Using Two 90° Elbows
HIGH ALTITUDE INSTALLATION
Your IHP direct vent fireplace has been tested and approved for elevations
from 0-2000 feet.
When installing a fireplace at an elevation above 2000 feet, you may need
to decrease the input rating by changing the existing burner orifice to a
smaller size. Reduce input 4% for each 1000 feet above sea level. Check
with your local gas company for proper orifice size identification.
When installing this fireplace at an elevation above 4500 feet, check with
local authorities.
PARTS LIST FOR VENTING KITS AND COMPONENTS
Catalog No.
J2209
J2201
J2203
J2205
J2207
J2082
J0661
J0663
J1504
J3190
J2300
J3479
J2251
J2249
J3134
J2292
J3483
J0373
J0953
J2316
Superiorfireplaces.US.com
IHP (5/8") Pipe & Vent Kits
Part No.
Description
P58-6
6" Section Double Wall Pipe, Galvanized
P58-12
12" Section Double Wall Pipe, Galvanized
P58-24
24" Section Double Wall Pipe, Galvanized
P58-36
36" Section Double Wall Pipe, Galvanized
P58-48
48" Section Double Wall Pipe, Galvanized
PA58-712
Adjustable 7"-12" Section Double Wall Pipe, Galvanized
E58-45
45° Elbow, Galvanized
E58-90
90° Elbow, Galvanized
HTS-58
Horizontal Square Termination, Galvanized
VT-58
Vertical Round Termination, Galvanized
SC-58
Storm Collar, Galvanized
WF-58
Wall Firestop, Galvanized
RF-58-6
Roof Flashing - 0 to 6/12 Pitch, Galvanized
RF-58-12
Roof Flashing - 6/12 to 12/12 Pitch, Galvanized
VR-58
Vertical Restrictor, Galvanized
S-58
Vinyl Siding Standoff, Galvanized
WS-58
Wall Strap
CS-58
Cathedral Ceiling Support
FP-58
Firestop Plate
SF-58
Stucco Flashing - For use with HTS-58
Venting with Two 90°
Elbows
Vertical
Horizontal
(V
)
(H)
1
6' min.
12' max.
7' min.
18' max.
8' min.
20' max.
20' max.
20' max.
V1 + V2 = 40' max.
126721-01B