1.3

FLUE TERMINAL POSITION

The minimum acceptable dimensions from the flue terminal to obstructions
and ventilation openings are shown below and listed in the table
It is important that the position of the flue allows the free passage of air
across it at all times. The minimum acceptable space from the flue terminal
to obstructions and ventilation openings are specified below in figure 2.
Fig. 2
DIMENSION TERMINAL POSITION
A
Directly below an opening, air brick,
opening window
B
Above an opening, air brick,
opening window
C
Horizontally to an opening, air brick,
opening window etc.
D
Below gutters, soil pipes or drain pipes
E
Below eaves
F
Below balconies or car port roof
G
From a vertical drain pipe or soil pipe
H
From an internal or external corner
I
Above ground roof or balcony level
J
From a surface facing the terminal
K
From a terminal facing the terminal
L
From an opening in the car port
M
Vertically from a terminal on the same wall
N
Horizontally from a terminal on the
same Wall
O
NOT APPLICABLE
P
NOT APPLICABLE
Q
NOT APPLICABLE
MINIMUM DIMENSION
300mm (12in)
300mm (12in)
300mm (12in)
300mm (12in)
600mm (12in)
300mm (12in)
600mm (24in)
300mm (12in)
600mm (24in)
600mm (24in)
1200m (48in)
1500mm(59in)
300mm (12in)
N/A
N/A
N/A
5