Power Requirements
Relay Contact Rating
Digital Inputs
Wire Size
L
W
Network Standard
ON
ORKS
Temperature Sensor Type
Temperature
Backlit
Range
Display
Heating
Control
Cooling
Control
Accuracy
Temperature
Minimum Deadband
Ambient
Operating
Conditions
Storage
Compliance
United States
Canada
Europe
Australia and
New Zealand
Shipping Weight
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
16
TEC22x1-3 L
W
ON
Networked Single Stage Thermostat
19 to 30 VAC, 50/60 Hz, 2 VA (Terminals RC and C) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
30 VAC, 1.0 A Maximum, 3.0 A In-Rush, Class 2 or Safety Extra-Low Voltage (SELV)
Voltage-Free Contacts across Terminal C to Terminals DI1 and DI2
Unshielded Twisted Pair - 22 AWG (0.6 mm Diameter) Minimum, 18 AWG (1.0 mm
Diameter) Recommended
64 Devices Maximum without repeater, 128 Devices Maximum with repeater; 6,250 ft
(1,905 m) Maximum Length (Bus Topology)
Local 10k ohm Negative Temperature Coefficient (NTC) Thermistor
-40.0°F/-40.0°C to 122.0°F/ 50.0°C in 0.5° Increments
40.0°F/4.5°C to 90.0°F/32.0°C
54.0°F/12.0°C to 100.0°F/38.0°C
±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
2F°/1C° between Heating and Cooling
32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
-22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
UL Listed, File E27734, CCN XAPX,
Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
L
M
® Certification 3.4 (pending)
ON
ARK
UL Listed, File E27734, CCN XAPX7,
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003
CE Mark, EMC Directive 89/336/EEC
C-Tick Mark, Australia/NZ Emissions Compliant
0.75 lb (0.34 kg)