Configuring Inputs DI1 and DI2
When DI1 and DI2 are configured for an alarm
condition, an alarm condition is displayed locally when
the input is closed. An alarm message is included on
the scrolling Status Display Menu and when the
message is displayed, the backlight momentarily
lights up.
Table 2: Installer Configuration Menu (Part 1 of 3)
Parameter
Description and Default
Appearing
on Display
1
Configuration of Digital Input 1.
DI1
Default: None
1
Configuration of Digital Input 2.
DI2
Default: None
Lockout
Selectable Lockout Levels for
limiting end-user keypad interaction.
Default: 0
6
TEC22x1-3 L
W
ON
® Networked Single Stage Thermostats Installation Instructions
ORKS
Each input can be configured to the Selection Options
included in Table 2.
Selection Options
(None): No function is associated with an input.
(Service): A Service alarm is displayed on the thermostat when the
input is energized. This input can be tied into the air conditioning unit
control card, which provides an alarm should there be a malfunction.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat.
(RemNSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
(None): No function is associated with an input.
(Service): A Service alarm is displayed on the thermostat when the
input is energized. This input can be tied into the air conditioning unit
control card, which provides an alarm should there be a malfunction.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat.
(RemNSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
Function
(0)
Occupancy
Access
Override
Permanent
Access
Temperature
Setpoints
Temporary
Access
Temperature
Setpoints
System Mode
Access
Setting
Fan Mode Setting
Access
Schedules
Access
4
Setting
4
Access
Clock Setting
Lockout Level
(1)
(2)
Access
No Access
No Access
No Access
Access
No Access
No Access
No Access
No Access
No Access
No Access
No Access
Access
Access