Table 2: Installer Configuration Menu (Part 3 of 3)
Parameter
Description and Default
Appearing
on Display
TOccTime
Sets the duration of the Temporary
Occupancy Time (when the
thermostat is in the Unoccupied
mode) when a Schedule Override
Function is enabled using either the
Main User Menu or DI1 or DI2
configured as a temporary override
remote contact (RemOVR).
Sets the effective duration of the
Temporary heating or cooling
setpoints set using the up/down
arrow keys.
default: 3.0 hrs
Cal RS
Sets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°C
Cal OS
Sets the desired outdoor air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°
H lock
Discontinues heating operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default: 120°F/49°C
C lock
Discontinues cooling operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default: -40°F/-40°C
Sets the number of events within a
4
2/4event
24-hour period.
Default: 2.0
Aux cont
Energizes peripheral devices
(lighting equipment, exhaust fans,
and economizers).
Default: n.o.
4
Provides the desired occupied
Prog rec
temperature either at the start of the
occupied schedule or after the
occupied schedule begins.
Note: Progressive recovery is
Default: off
8
TEC22x1-3 L
W
ON
disabled if either DI1 or DI2
is configured as remote
NSB.
® Networked Single Stage Thermostats Installation Instructions
ORKS
Selection Options
Range: 0.0 to 12.0 hrs adjustable in 1-hour increments
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C°
increments
Range: -5.0F°/-2.5C° to 5.0F°2.5C° adjustable in 1.0F°/0.5C°
increments
Range: -15°F/-26°C to 120°F/49°C adjustable in 5F°/5C° increments
Range: -40°F/-40°C to 95°F/35°C adjustable in 5F°/5C° increments
(2.0): Two events (one occupied and one unoccupied) within a
24-hour period
(4.0): Four events (two occupied and two unoccupied) within a
24-hour period
(n.c.): Contact open = Occupied; contact closed = Unoccupied
(n.o.): Contact closed = Occupied; contact open = Unoccupied
The contact toggles with the internal Occupied/Unoccupied
schedule (or the NSB contact on one of the digital inputs, if used).
(on): Enabled (provides the desired occupied temperature at the
start of the occupied schedule)
(off): Disabled (provides the desired occupied temperature after the
occupied schedule begins)