Table 2: Installer Configuration Menu (Part 2 of 3)
Parameter
Description and Default
Appearing
on Display
Sets the delay time period at
2
Pwr del
thermostat power up, or at each
time power is removed and
reapplied, before any operation
(fan, heating, or cooling) is
authorized. Also can be used to
sequence the startup of multiple
units in one location.
Default: 10.0 sec
Frost pr
Provides a minimum heating
setpoint of 42.0°F/5.5°C to prevent
freezing in the zone controlled by
the thermostat.
Default: off
3
Sets the Occupied and Unoccupied
Heat max
maximum Heating setpoint values.
Default: 90.0°F/32.0°C
3
Sets the Occupied and Unoccupied
Cool min
minimum Cooling setpoint values.
Default: 54.0°F/12.0°C
Anticycl
Anti-Short Cycle timer sets the
minimum on/off times for heating
and cooling stages.
Default: 2.0 min
Heat cph
Sets the maximum number of
Heating cycles per hour.
Default: 4.0
Cool cph
Sets the maximum number of
Cooling cycles per hour.
Default: 4.0
Deadband
Sets the minimum deadband
between the heating and cooling
setpoints.
Default: 2.0F°/1.0C°
Fan cont
Determines how the fan is activated
in response to a call for heating.
Fan cont applies to W1 and W2 and
Fan Mode auto only. Fan cont does
not affect fan operation on a call for
cooling (Y1 and Y2).
Default: on
Fan del
Fan delay extends fan operation
after a heating or cooling cycle has
ended.
Default off
TEC22x1-3 L
W
® Networked Single Stage Thermostats Installation Instructions
ON
ORKS
Selection Options
Range: 10.0 to 120.0 sec
(on): Enabled
(off): Disabled
Range: 40.0°F/4.5°C to 90.0°F/32.0°C
Range: 54.0°F/12.0°C to 100.0°F/37.5°C
Range: 0.0 to 5.0 min adjustable in 1-minute increments
Set the anti-short cycle timer to 0.0 min for equipment that already
has its own anti-short cycle timer.
Range: 3.0 to 8.0 cycles per hour
Range: 3.0 or 4.0 cycles per hour
Range: 2.0F°/1.0C° to 4.0F°/2.0C° adjustable in 1.0F°/0.5C°
increments
(off): The thermostat will not activate the fan in response to a call
for heating. The fan is activated by the equipment fan and limit
control.
(on): Enables the thermostat to activate the fan in response to a call
for heating or cooling.
(on): Extends fan operation by 60 seconds after a heating or cooling
cycle has ended.
(off): No extension of fan operation after a heating or cooling cycle
has ended.
The fan delay is only active when the fan is in the Auto mode.