Section Ii: Masonry Insert Installation - New Buck Corporation 85 Instruction Manual

Non-catalytic unit
Hide thumbs Also See for 85:
Table of Contents

Advertisement

The Model 85 may be installed using an all masonry fireplace built in accordance with
Uniform Building Code and National Fire Protection Association (NFPA). The first step in
this type of installation is to determine acceptability of fireplace and chimney for use with a
woodstove. Both construction and condition of fireplace are important considerations when
installing a woodstove. The chimney should extend at least 3' above roof and at least 2' above
any point of roof within 10'.
REMEMBER TO HAVE YOUR CHIMNEY INSPECTED FOR LEAKS AND BLOCKAGE
BEFORE YOU INSTALL YOUR STOVE. "DO NOT CONNECT THIS UNIT TO A
CHIMNEY FLUE SERVING ANOTHER APPLIANCE."
MINIMUM CLEARANCE MASONRY INSERT
MODEL 85
A. Side Wall Combustible
B. Front Floor Protector
C. Side Floor Protector
D. Side Wood Trim
E. Top Wood Trim
F. Mantel or Brackets
1. The hearth must be of masonry construction and must extend a minimum of 16" in front of
firebox opening and a minimum of 8" to either side of firebox opening.
If there is not minimum hearth protection from front of firebox opening and front of ma-
2.
sonry hearth, a floor protector must be used in front of hearth to protect combustible
materials. The floor protector must be 3/8" minimum thickness non-combustible material
or equivalent.(See Page 6.)
SECTION II
MASONRY INSERT INSTALLATION
CAUTION
12"
16"
8"
7"
10"
21"
C
A
Page 5
E
F
D
B