1. Select an installation location that will give best airflow from front of heater to remainder of home.
2. Place protective floor pad in position. For minim floor protection (See Page 24).
3. Place unit on pad making sure minimum clearance specifications are met. For minimum
clearance to combustibles (See Page 22).
4. Lightly mark with a pencil location of pedestal on protective pad.
5. Next, remove four (4) screws holding heater to stand. Position heater out of way of installation area.
6. Check that pedestal stand is still aligned with marks on protective pad, now mark outside air opening in
bottom of pedestal stand on to pad.
7. Mark center line of outside air opening. Set stand aside for now.
8. Cut a 4 1/4" diameter hole in pad and continue through floor.
The structural integrity of home floor must be maintained. (Move opening
9. Now, reposition pedestal stand and set on pad being sure to line stand up with reference marks.
10. Using an electric drill and 3/8" masonry bit, drill four (4) holes in protective pad using holes in bottom of
pedestal stand as a guide. Be careful to drill only through pad and not into floor. Change bit to a 1/4" metal
bit and drill through floor.
11. Using four (4) 3/8" x 1-1/2" lag bolts provided, secure pedestal stand and pad to floor of home.
IF A THICK FLOOR PROTECTOR IS USED, YOU MAY HAVE
12. Obtain the outside air duct from box in pedestal kit marked FA P21B.
13. Slip duct down through the 4-1/4" hole until face of outside air duct with screen wire, contacts
bottom of pedestal.
14. Secure outside air duct to inside bottom of pedestal using four (4) #10x1 screws provided.
(See Figure 12B).
15. Set heater back onto stand and resecure using screws.
16. NOTE: If home is underpinned, you must duct through underpin as shown. (See Figure 12C).
(4) 3/8" x 1-1/2"
FLOOR PROTECTOR PAD
UNDER SIDE OF MOBILE HOME FLOOR
CAUTION!!
and/or reposition heater location if necessary).
CAUTION:
TO USE LONGER LAG BOLTS.
Figure 12B
OUTSIDE AIR DUCT
PEDESTAL
(4) #10x1
OUTSIDE AIR DUCT THROUGH FLOOR WHEN
MOBILE HOME IS NOT UNDERPINNED.
Page 26
Figure 12C
OUTSIDE AIR DUCT THROUGH
UNDERPINNED.