Section Ii: Masonry Insert Installation - New Buck Corporation 21 Manual

Non-catalytic unit
Table of Contents

Advertisement

The Model 21 may be installed using an all masonry fireplace built in accordance with the
Uniform Building Code and National Fire Protection Association (NFPA). The first step in
this type of installation is to determine the acceptability of the fireplace and chimney for use
with a woodstove. Both the construction and condition of the fireplace are important consid-
erations when installing a woodstove. The chimney should extend at least 3' above the roof
and at least 2' above any point of the roof within 10'.
REMEMBER TO HAVE YOUR CHIMNEY INSPECTED FOR LEAKS AND BLOCKAGE
BEFORE YOU INSTALL YOUR STOVE. "DO NOT CONNECT THIS UNIT TO A
CHIMNEY FLUE SERVING ANOTHER APPLIANCE."
MINIMUM CLEARANCES TO FLOOR AND COMBUSTIBLES
MINIMUM CLEARANCE MASONRY INSERT
MODEL 21
A. Side Wall Combustible
B. Front Floor Protector
C. Side Floor Protector
D. Side Wood Trim
E. Top Wood Trim
F. Mantel or Brackets
1. The hearth must be of masonry construction and must extend a minimum of 16" in front of
the firebox opening and a minimum of 6" to either side of the firebox opening.
2. If there is not minimum hearth protection from the front of the firebox opening and the
front of the masonry hearth, a floor protector must be used in front of the hearth to
protect combustible materials. The floor protector must be 3/8" minimum thickness non-
combustible material or equivalent.(See Page 5.)
SECTION II
MASONRY INSERT INSTALLATION
CAUTION
25"
16"
6"
17"
17"
25"
C
A
4
E
F
D