YASKAWA VS mini C Series Instruction Manual page 61

Ultra-compact all digital inverter advanced function type
Hide thumbs Also See for VS mini C Series:
Table of Contents

Advertisement

<Corrective
Actions
of Models'with
Digital
Operator>
• . ,,_- : ON
(_ : BLINKING
: OFF
Alarm
Display
and Contents
Alarm Display
Inverter
Causes and
Digital
RUN (Green)
Status
Explanation
Operator
ALARM IRedl
Corrective Actions
EF (Simultaneous FWD/ Check SF and SR input
REV runcommands)
terminals.
When FWD and REV
E/:::
run commands are
simultaneously input
Blinking
for over 500ms, the
inverter stops according
to constant nO3.
-.,_-
BS (External baseblock) Check multi-function
Base block command at
input terminals $1, S2,
.O
multi-functionterminalis
or $3.
bb
active, the inverter output
or
isshutOFF (rno_r_)
Blinking
6
Tempora,.y cond._, (:feared
,.
when input command is
removed.
Warning
STP (Operator function
Check terminals
Fault
stop)
SF and SR.
contacts _
S_P
do not
is pressed
change
:luring running by the
Blinking
state.
:ontrol circuit terminals
3F and SR. The inverter
;tops according to
.'onstant nO3.
OL 3 (Overtorque
Check the driven
detection)
machine and correct
Motor current exceeded
the cause of the fault, or
o;
3
the preset value in
increase the value of
Blinking
constant n51.
constant n51 upto the
fnverter continues
highest value allowed for
operation,
the machine.
:,_-
(_
SEr (Sequence error)
Check the multi-function
Inverter receives
input terminals S1, S2,
LOCAL/REMOTE
and $3.
SE*'-
select command from
Ihe multi-functionterminal
Blinking
while the inverter is
outpetting.
Refer
to page
39 for LOCAL/REMOTE
select signal.
61