Preventing Motor From Stalling (Current Limit) - YASKAWA VS mini C Series Instruction Manual

Ultra-compact all digital inverter advanced function type
Hide thumbs Also See for VS mini C Series:
Table of Contents

Advertisement

I
Preventing
motor
stalling
(Current
limit)
I
from
Automatically
adjusts
the output
frequency
and output
current
according
to
• the load to (zontinue operation
without
stalling the motor.
• Stall prevention
(current
limit) level during
acceleration
(n34)
Sets the stall prevention
(current
limit)
level during
acceleration
in units of
1%.
(Inverter
rated current
= 100%)
Factory
setting:
170%
A setting
of 200%
disables
the stall
prevention
(current
limit)
during
acceleration.
During
acceleration,
if the output
current
exceeds
the value
set
for n34, acceleration
stops and frequency
is maintained.
When
the output
current
goes down
to the value
set for n34, acceleration
starts.
MOTOR CURRENT
n34 .........
OUTPUT"
i
• T_M_
FREOUENCY
i
• _
: TME
prevent the motor from stalling.
In the constant
output
area [output
frequency
->_max. voltage
output
frequency
(n26)],
the stall
prevention
(current
limit)
level
during
acceleration
is changed
by the following
equation.
Stall prevention (current limit) level[
[during acce in constant output areaJ
_ _ Stall prevention
(current limit) I X IMax" voltage output frequency (n26)1
i
evel during accel (n34)
lOut_put frequency)
54