Installer Setup Menu - Lennox Commercial TouchScreen Thermostat Installation Instructions Manual

Commercial touch screen thermostat
Hide thumbs Also See for Commercial TouchScreen Thermostat:
Table of Contents

Advertisement

Installer
Installer
Setup No.
Setup Name
Date (Year
0120
Upper)
Date (Year
0130
Lower)
0140
Date (Month)
0150
Date (Day)
Schedule
0160
Options
System
0170
Selection
TOD/Econo-
0175
mizer output
(terminal A)
Heat Fan
0180
Operation
Pre−occupan-
0185
cy Purge
Duration
Reversing
0190
Valve O/B
Cycles Per
Hour (CPH)
0220
for first stage
compressor
CPH for
second stage
0230
compressor
CPH for first
stage conven-
0240
tional heat
CPH for sec-
0250
ond stage con-
ventional heat
CPH for third
0260
Stage Heat
CPH for Auxil-
0270
iary Heat
Table 3. Installer Setup Menu
Default
All Settings
Setting
20−22xx
20
21−21xx
04
00−99
6
1−12
15
1−31 (Month Dependent)
0−Non−Programmable
4
4−Programmable
1−1H/1C
2−1H/1C HP*
3−1H w/o fan
4−1H with fan
6−1C
7−2H/1C HP*
8
8−2H/2C Conv
9−2H/1C Conv
10−1H/2C Conv
11−2H/2C HP*
12−3H/2C HP*
0−Unused
0
1−TOD
2−Economizer
0−Fossil
0
1−Electric
0−No duration
1−One hour
0
2−Two hours
3−Three hours
0−O (O/B On Cool)
0
1−B (O/B On Heat)
3
1−6
3
1−6
5
1−12
5
1−12
9
1−12
9
1−12
Page 7
Notes
Available year range:2001−2178
Available year range:2001−2178
*Setting not used with Lennox commercial
equipment.
Economizer energizes A during a call for cool.
TOD energizes A during Occupied period and
de−energizes A during Unoccupied. Use
1−TOD.
Only shown for conventional system with heat
stages and fan capability selected. If heat pump
is selected, fan defaults to electric.
Shown only if system has fan and schedule
programmable. Pre−occupancy purge enabled
by nonzero duration (and sends economizer to
minimum position).
O or B setting not used with Lennox commer-
cial equipment.
Only shown for system with cool stages.
Selection in this stage changes default CPH of
second stage cool.
Only shown if two stages of cool selected.
Only shown if system is conventional with heat
stages.
Selection in this stage changes default CPH of
second stage heat.
Only shown with at least two stages conven-
tional heat or 2H/1C heat pump selected.
Only shown if 3H/2C heat pump is selected.
Only shown if multi−stage heat pump is se-
lected
(heat pump with more heat than cool stages).
table continued on next page