Lennox Commercial TouchScreen Thermostat Installation Instructions Manual page 8

Commercial touch screen thermostat
Hide thumbs Also See for Commercial TouchScreen Thermostat:
Table of Contents

Advertisement

Installer
Installer
Setup No.
Setup Name
Continuous
0280
Backlight
0300
Changeover
0310
Deadband
Temperature
Indication
0320
Scale
Daylight
0330
Saving
Remote
Temperature
0340
Sensor
Heat Pump
0350
Compressor
Lockout
Heat Pump
0360
Auxiliary Lock-
out
Temporary
0535
Occupied
Duration Limit
Number of Pe-
0540
riods
505103M 11/08
Table 3. Installer Setup Menu
Default
All Settings
Setting
0−No
0
1−Yes
0−Manual
1
1−Auto
2
(1.5)−2°F (1.5°C)
3
(2.0)− 3°F (2.0°C)
4
(2.5)− 4°F (2.5°C)
3°F
5
(3.0)− 5°F (3.0°C)
(2°C)
6
(3.5)− 6°F (3.5°C)
7
(4.0)−7°F (4.0°C)
8
(4.5)− 8°F (4.5°C)
9
(5.0)− 9°F (5.0°C)
0−°F
0
1− °C
0−Disabled,
1−Enabled (US, 1987)
2
2−Enabled (2007),
3−Enabled (Europe)
0−None
1−Outdoor for Display
0
2−Outdoor for Control
3−Remote 10K Indoor
4−Remote 20K Indoor
0− None
15(−9.5)−15°F(−9.5°C)
20(− 6.5)−20°F(− 6.5°C)
25(− 4.0)−25°F(− 4.0°C)
0
30(− 1.0)−30°F(− 1.0°C)
35(1.5)−35°F(1.5°C)
40(4.5)−40°F(4.5°C)
45(7.0)−45°F(7.0°C)
0− None
40(4.5)−40°F(4.5°C)
45(7.0)−45°F(7.0°C)
0
50(10.0)−50°F(10.0°C)
55(13.0)−55°F(13.0°C)
60(15.5)−60°F(15.5°C)
0−None
1−one hour
3
2−two hours
3−three hours
4− four hours
2− 2 Periods
4
4− 4 Periods
Page 8
Notes
Always shown. If AC power not present the
option is overridden and normal backlight op-
eration occurs.
Only shown if system has both heat and cool
stages.
Only shown if Automatic Changeover Selected
Averaging would not include on− board sensor.
It is accomplished by series/parallel combina-
tions. 2 applies only to Heat Pump applications
(allowing compressor lockout while displaying
temperature). Set for total equal resistance for
combination of sensors.
Lennox commercial equipment does not use
heat pump mode. Only shown for heat pump
systems with more heat stages than cool
selected and remote sensor selection is out-
door for control. Must enforce a dead band
between this and Auxiliary Lockout
Lennox commercial equipment does not use
heat pump mode. Only shown for heat pump
systems with more heat stages than cool se-
lected and remote sensor selection is outdoor
for control. Must enforce a dead band between
this and Heat Pump Compressor Lockout.
0 means no limit
Does not appear if Non− programmable is cho-
sen. Applies to all days of the week. With 2
selected the Cancel Period option does not
appear on the display.
table continued on next page