Connecting The Host Computer; Attaching The Ups Front Bezel; Selecting The Ups Voltage Configuration; Connecting The Serial Communications Port - HP R1500 Generation 3 Installation Instructions Manual

Hide thumbs Also See for R1500 Generation 3:
Table of Contents

Advertisement

NOTE: A small amount of arcing may occur when
connecting the batteries. This is normal and does not
damage the unit or present any safety concern.
Connect the battery lead to the battery terminal.

Attaching the UPS front bezel

Selecting the UPS voltage
configuration
Using a small tool, position the DIP switches according to the desired
voltage configuration.
NOTE: An asterisk (*) indicates the default setting.
Output
voltage
R1500 G3
100 V*
JPN/TWN
110 V
110 V
R1500 G3
NA
120 V*
R1500 G3
220 V
INTL
230 V*
240 V

Connecting the host computer

CAUTION: Only one communications port can be
connected to the host computer. Connecting more than
one will result in unexpected UPS behavior. If an option
card is installed, the serial and USB communications ports
are automatically disabled.
Connect the UPS to a host computer using either the USB cable or the
DB9 serial cable included with the UPS. Install HP Power Protector on
the host computer. See the HP website
(http://www.hp.com/go/rackandpower) to download the latest
version of HP Power Protector.
NOTE: To install and configure the software, see the
software user guide. The software user guide is available
for download from the HP website
(http://www.hp.com/go/rackandpower).

Connecting the serial communications port

CAUTION: Use only the computer interface cable
supplied with the UPS to connect the communications port
to the host computer.
IMPORTANT: Power management software requires the
communications port to be appropriately cabled to the
host computer.
For information about serial port pin assignment, see "Serial
communications port pin assignment" in the user guide.
Input voltage
DIP
DIP switch
range
switch 1
2
90–106 V
Down
Down
99–116 V
Down
Up
99–116 V
Down
Up
108–127 V
Up
N/A
198–233 V
Down
Up
207–243 V
Up
N/A
216–254 V
Down
Down