Ups System Installation; Preliminary Installation Information; Unloading The Ups Cabinet From The Pallet - Eaton 93E Operation Manual

300/400 kva (380/400/415v)
Table of Contents

Advertisement

Chapter 4

UPS System Installation

4.1

Preliminary Installation Information

Installation should be performed only by qualified personnel. See installation instructions before
connecting to the supply.
Refer to the following while installing the UPS system:
• Chapter 3 for cabinet dimensions, equipment weight, wiring and terminal data, and installation notes.
• Do not tilt the cabinets more than
• If perforated floor tiles are required for ventilation, place them in front of the UPS.
• The UPS unit is not suitable for IT or corner-earthed power distribution systems.
• Suitable for mounting on concrete or other non-combustible surfaces only
4.2
Unloading the UPS Cabinet from the Pallet
The UPS Cabinet is bolted to a wooden pallet supported by wood skids. To remove the pallet:
The UPS cabinet is heavy (see Table 3-1). If unpacking and unloading instructions
are not closely followed, the cabinet may tip and cause serious injury.
• Do not tilt cabinet more than 15° from vertical.
• Lift the cabinets only with a forklift or damage may occur.
1.
If not already accomplished, use a forklift or pallet jack to move the UPS cabinet to the installation area, or
as close as possible, before unloading from the pallet. Insert the forklift or pallet jack forks between the
supports on the bottom of the pallet (see Figure 3-3 for the UPS cabinet centre of gravity measurements).
2.
Remove four bolts securing the shipping bracket to the cabinet and four bolts securing the bracket to the
pallet (see Figure 4-1). Remove the shipping bracket. If installing the cabinet permanently, retain the
shipping bracket and securing hardware for later use.
3.
Roll the cabinet to the final installation location.
4.
If permanently mounting the system, proceed to Step 11;
5.
Using the retained hardware, reinstall the shipping brackets removed in Step 2 a to the front and rear of the
UPS cabinet with the angle facing outward (see Figure 4-1).
6.
Secure the cabinet to the floor with hardware.
±
NOTE
For the following steps, verify that the forklift or pallet jack is rated to handle the
weight of the cabinet (see Table 3-1 for cabinet weight).
WARNING
15° during installation.
WARNING
CAUTION
Eaton 93E UPS (300/400 kVA, 380/400/415V) Installation and Operation Manual
4-1

Advertisement

Table of Contents
loading

This manual is also suitable for:

93e-400/30093e-400/400

Table of Contents