Chapter 9
Product Specifications
9.1 Model Numbers
The UPS is housed in a free-standing cabinet with safety shields behind the door. The UPS is available in
50 or 60 Hz with various output power ratings.
Models
Eaton 93E-400/300
Eaton 93E-400/400
9.2 Specifications
The following sections detail the input, output, environmental, and battery specifications for the UPS.
9.2.1 UPS Input
Operating Input Voltage
Input Voltage Range
Operating Input Frequency Range
Input Frequency Range Range
Operating Input Current
Input Current Harmonic Content
Power Factor
Line Surges
Battery Voltage
Battery Charging Capacity
Power Rating
300 kVA
400 kVA
380/400/415 Vac
190/330–276/478V (-15%, +20%) at 100% load
116/201-276/478V (-50%, +20%) at 50% load
50/60 Hz
40-72Hz
See Table 3-5.
Adjustable
5% THD at full load
Minimum 0.99
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801 4
480 Vdc
160A maximum at any load up to100% load for 300KVA UPS
160A maximum at any load up to100% load for 400KVA UPS
Eaton 93E UPS (300/400 kVA, 380/400/415V) Installation and Operation Manual
Frequency
50/60 Hz
50/60 Hz