UPS Installation Plan and Unpacking
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the weight requirements shown in Table 3-1 and the
size requirements shown in Figure 3-1. Dimensions are in millimetres (inches).

Table 3-1. UPS Cabinet Weights

The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are in the back of the cabinet. Allow clearance in front of and in back of the cabinet
for proper air circulation. The clearances required around the UPS cabinet are shown in Table 3-2.

Table 3-2. UPS Cabinet Clearances

From Top of Cabinet
From Front of Cabinet
From Back of Cabinet
From Right Side of Cabinet
From Left Side of Cabinet
The basic environmental requirements for operation of the UPS are:
• Ambient Temperature Range: 0–40°C (32–104°F)
• Recommended Operating Range: 20–25°C (68–77°F)
• Maximum Relative Humidity: 95%, noncondensing

Table 3-3. 93E Required Clearance

A : 93E Required Clearance for paralleled adjacent UPS or UPS and adjacent PDU
ambient
25
C
o
30
C
o
35
C
o
40
C
o
B : 93E Recommended Clearance for UPS with adjacent battery cabinet
ambient
25
C
o
Notes:
• L1- clearance to the rear wall.
• L2- clearance between the adjacent paralleled UPS or UPS and adjacent PDU. Parallel UPS should be as
close as possible.
• L3- clearance between the UPS and battery cabinet.
3-2
Eaton 93E UPS (300/400 kVA, 380/400/415V) Installation and Operation Manual
Model
Eaton 93E-400/300
Eaton 93E-400/400
300 mm (12") working space
900 mm (36") working space
See Table No:3-3
See Table No:3-3
See Table No:3-3
300kVA
L1(mm)
L2(mm)
L1(mm)
≥250
≥300
≤50
≥400
≥500
300kVA
L1(mm)
L3(mm)
L1(mm)
≥600
≥2500
≥800
≥2000
≥1000
≥200
Weight
kg (lb)
Shipping
1090 (2403)
400kVA
L2(mm)
≥250
≥300
≤50
≥400
≥500
400kVA
L3(mm)
≥600
≥2500
≥800
≥2000
≥1000
≥200
Installed
970 (2138)