Figure 3-3. Ups Cabinet Centre Of Gravity; Table 3-4. Air Conditioning Or Ventilation Requirements During Full Load Operation - Eaton 93E Operation Manual

300/400 kva (380/400/415v)
Table of Contents

Advertisement

UPS Installation Plan and Unpacking
If battery systems are located in the same room as the UPS, the battery manufacturer's
environmental requirements should be followed if they are more stringent than the UPS
requirements. Operating temperatures above the recommended range will result in decreased
battery life and performance, and may reduce or void the battery warranty.
The UPS ventilation requirements are shown in Table 3-4.

Table 3-4. Air Conditioning or Ventilation Requirements During Full Load Operation

Model
Eaton 93E-400/300
Eaton 93E-400/400
3-4
Eaton 93E UPS (300/400 kVA, 380/400/415V) Installation and Operation Manual
Front View

Figure 3-3. UPS Cabinet Centre of Gravity

Rating
Input/Output Voltage
300 kVA
380/380 400/400 415/415
400 kVA
380/380 400/400 415/415
Dimensions are in millimetres [inches]
CAUTION
Heat Rejection
BTU/hr x1000 (kg-cal/hr)
46.45 (11709)
82.59(20816)
Right View