Figure 26. Supervisory Contact Module - Powerware 9315 Installation Manual

100 kva -- 160 kva
Hide thumbs Also See for 9315:
Table of Contents

Advertisement

26 provides contacts for monitoring UPS status. A maximum of two monitoring
accessories (RMPs, RIMs, or SCMs) can be installed. Refer to Chapter 10, Table D
for the number of accessories permitted. See Drawing 164200292---12 in Appendix
A for enclosure dimensions, side views, and knockout patterns.
To install a Supervisory Contact Module:
1.
Securely mount the SCM.
2.
Install wiring from the SCM using ½-in. conduit through the
either the top or bottom of the UPS cabinet.
The top entry connection requires installation of ½-in. flexible conduit within the
UPS. Bottom entry connection requires no additional routing of conduit within
the UPS.
3.
If not already installed, locate the RMP adapter cable assembly (see Figure 27)
in the spare parts kit. Mate the DE---9 connector on the back of the terminal
block into the DE---9 connector on the Communications Panel of the UPS (see
Figure 28). Use two screws from the spare parts kit to secure the terminal
block bracket to the Communications Panel.
Powerware 9315 (100 kVA- -160 kVA) Installation
164200292 Rev. E 041500
Installing a Supervisory Contact
The optional Supervisory Contact Module (SCM) as shown in Figure

Figure 26. Supervisory Contact Module