Checking The Gas Rate; Domestic Hot Water - Worcester GREENSTAR 24i Junior Installation Instructions Manual

Wall hung rsf gas-fired condensing combination boiler
Table of Contents

Advertisement

5.6.2

CHECKING THE GAS RATE

B The gas rate should be measured at the gas meter
after 10 minutes operation at maximum.
See technical data section at the front of this manual.
B Where a gas meter is not available (e.g. L.P.G.) the
CO/CO
must be checked to the units shown in the
2
setting of the air/gas ratio, refer to section 6.6.
B If pressure and gas rate are satisfactory press the
service button again and the boiler will return to
normal operation.
– If left in the service mode the control will return to
normal operation after 15 minutes.
B Close the gas isolation valve.
B Remove the manometer.
B Re-seal the screw in the gas inlet pressure test point.
B Open the gas isolation valve.
B Ensure that there are no gas leaks.
B Replace the outer case.
5.6.3

DOMESTIC HOT WATER:

Controlling the hot water temperature:
The hot water temperature is set to approximately 55°C
at the factory.
DOMESTIC HOT WATER PRE-HEAT:
Pre-heat reduces the time taken to produce hot water at
the tap and is controlled by the ECO button.
B Press the ECO button to select either state:
– When the ECO button is not illuminated the boiler
will be in pre-heat mode (which will reduce the
time taken to produce hot water at the tap).
– OR
– When the ECO button is illuminated the boiler will
be in Economy mode with pre-heat no longer
active.
6 720 644 741a (2010/10)
COMMISSIONING
41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Greenstar 28i junior

Table of Contents