INSTRUCTION MANUAL INSTALLATION, COMMISSIONING & SERVICING WALL HUNG RSF GAS FIRED CONDENSING COMBINATION BOILER GREENSTAR 24i j j u u n n i i o o r r / 28i j j u u n n i i o o r r FOR SEALED CENTRAL HEATING SYSTEMS AND MAINS FED DOMESTIC HOT WATER THE APPLIANCE IS FOR USE WITH...
L.P.G. CONVERSION FAULT FINDING & DIAGNOSIS FAULT FINDING CENTRAL HEATING FUNCTION PREHEAT AND DHW FUNCTION PROTECTION FUNCTION BENCHMARK CHECKLIST SERVICE INTERVAL RECORD SHEET INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior CONTENTS 8 716 115 166b (03/2009)
32 F LU E AI R P R ES S U R E SWITC H CONNECTION (BLANKED OFF ON THIS APPLIANCE) INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior LAYOUT & COMPONENTS 8 716 115 166b (03/2009)
Page 8
50 CH TEMPERATURE CONTROL 51 POSITION FOR OPTIONAL PROGRAMMER 52 SERVICE MODE BUTTON 53 BURNER ON INDICATOR LIGHT (GREEN) 54 MASTER SWITCH ON/OFF INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior LAYOUT & COMPONENTS 8 716 115 166b (03/2009)
• It may be necessary to use a power flushing machine to aid the cleansing procedure in some circumstances INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior CLEANING PRIMARY SYSTEMS 8 716 115 166b (03/2009)
In such circumstances, the advice of the local water authority should be sought. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior MAINS SUPPLY 8 716 115 166b (03/2009)
• Do not use galvanised pipes or radiators. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior WATER SYSTEMS & PIPEWORK 8 716 115 166b (03/2009)
An air break must be installed in the 32/43 mm pipework, between the boiler condensate outlet and the drainpipe, outside the property, to avoid flooding during adverse weather conditions. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior CONDENSATE PIPEWORK 8 716 115 166b (03/2009)
Minimum level area 122 cm free area 61 cm Minimum free Minimum level area 122 cm free area 61cm INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior BOILER LOCATION & CLEARANCES 8 716 115 166b (03/2009)
Additional RCD (Residual Current Device) pro- tection may be required. Refer to the latest IEE wiring regulations. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior BOILER LOCATION & CLEARANCES 8 716 115 166b (03/2009)
Further guidance on pipe routing can be found printed on the boiler template (supplied with the boiler). Mains Gas Mains Water Supply 22mm (DHW IN) 15mm INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior PLUMBING MANIFOLD 8 716 115 166b (03/2009)
Maximum total flue length 28 i jun. 2,400mm 11,000mm 100mmØ 125mmØ 24 i jun. 2,600mm 11,000mm 28 i jun. 2,600mm 11,000mm INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior FLUE OPTIONS 8 716 115 166b (03/2009)
50 mm) around the flue and fixed to the wall with plated screws. See Contact Information (inside front cover). INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior FLUE TERMINAL POSITIONS 8 716 115 166b (03/2009)
Page 19
FLUE TERMINAL POSITIONS INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior FLUE TERMINAL POSITIONS 8 716 115 166b (03/2009)
This kit can be used in conjunction with the optional filling loop 7 716 192 281(not sup- plied with the boiler). INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior WALL MOUNTING PLATE FLUE OPENING 8 716 115 166b (03/2009)
6.2). Remove any packaging within the boiler and the packaging base (C). CAUTION: Caps fitted to pipes must be removed before hanging the boiler. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior UNPACKING THE APPLIANCE 8 716 115 166b (03/2009)
UP until the stop on the inside of the handle is over the shoulder of the metal bracket to secure in place. Stop in locked position INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior BOILER CONNECTIONS 8 716 115 166b (03/2009)
Page 24
15mm compression joint (J) using the compression nut and olive supplied in the hardware literature pack. 22mm 15mm 22mm 15mm 22mm INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior BOILER CONNECTIONS 8 716 115 166b (03/2009)
After cutting, the end must be square and free from burrs to prevent damage to the 130mm flue seals. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior FLUE INSTALLATION 8 716 115 166b (03/2009)
Page 26
Do not attempt to force beyond the limit stops. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior FLUE INSTALLATION 8 716 115 166b (03/2009)
Page 27
• The flue is set at an angle of 3° or 52mm per 1m length. Flat at back This screw should be fitted last for rear exit INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior FLUE INSTALLATION 8 716 115 166b (03/2009)
Re-fit the drainage cap to bottom of the syphon. DRAINAGE CAP DISCHARGE HOSE WALL FRAME CONNECTOR INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior CONDENSATE CONNECTION 8 716 115 166b (03/2009)
5 Optional external frost stat connection (ST6): Connect froststat cables to terminals (FS) and (FR). These are not polarity sensitive. 6 Refit panels. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior ELECTRICS 8 716 115 166b (03/2009)
POSITION OF WIRED COMPONENTS INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior POSITION OF WIRED COMPONENTS 8 716 115 166b (03/2009)
This kit can be used in conjunction with the optional filling loop 7 716 192 281(not sup- plied with the boiler). INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior FILLING THE SYSTEM 8 716 115 166b (03/2009)
To reset press and hold the reset button (E) for 2 seconds. The boiler will be reset. CAUTION: DO NOT PRESS POWER INDICATOR (B) TO RESET BOILER. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior STARTING THE APPLIANCE 8 716 115 166b (03/2009)
The addition of sealing agents to the system water is not recommended as this can cause problems with deposits left in the heat exchanger. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior WATER TREATMENT 8 716 115 166b (03/2009)
When the ECO button is illuminated the boiler will be in Economy mode with pre-heat no longer active. Inlet Test Nipple INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior COMMISSIONING 8 716 115 166b (03/2009)
If the appliance is unused and exposed to freezing conditions, shut off all the mains supplies and drain the system and boiler. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior FINISHING COMMISSIONING 8 716 115 166b (03/2009)
Commissioning. Operate the appliance and take note of any irregularities. Refer to Fault Finding for rectification procedures. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior INSPECTION AND SERVICE 8 716 115 166b (03/2009)
Page 38
2.1 Remove screw (C) securing control. 2.2 Gently pull the control forward until it is fully lowered into the service position. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior INSPECTION AND SERVICE 8 716 115 166b (03/2009)
Page 39
28i junior - 3.9 mbar 28i junior - 4.6mbar • Pressures measured below these figures will indicate that the heat exchanger will require cleaning. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior INSPECTION AND SERVICE 8 716 115 166b (03/2009)
Page 40
Catch the debris and condensate from the syphon into a suitable container. Re-fit the drainage cap (E) to bottom of the syphon. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior INSPECTION AND SERVICE 8 716 115 166b (03/2009)
Page 41
(K). Remove clamping plate (L). Remove spark/flame electrode assembly from boiler. Remove seal from the top of the heat exchanger. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior INSPECTION AND SERVICE 8 716 115 166b (03/2009)
Page 42
BETWEEN THE AIR/GAS MANIFOLD AN D TH E H EAT E XCHANG E R I S DISTURBED THE SEALING GASKET MUST BE REPLACED. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior INSPECTION AND SERVICE 8 716 115 166b (03/2009)
Undo the flue connection from the sump and push the flue tube up. Push the flue limit thermostat outwards from the sump. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior REPLACEMENT OF PARTS 8 716 115 166b (03/2009)
Page 44
Replace valve with new seals and check for gas soundness. Note: The valve will require setting; follow procedure “Setting the air/gas ratio” . INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior REPLACEMENT OF PARTS 8 716 115 166b (03/2009)
Page 45
Remove 5 screws (C) retaining the rear panel of the control and remove panel. Spare Fuse order T1.6L 250V F2 T2.5H 250V F1 T500L 250V F3 INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior REPLACEMENT OF PARTS 8 716 115 166b (03/2009)
Page 46
IS RE-FITTED TO THE NEW CONTROL. IF THIS IS NOT DONE THE BOILER WILL INDICATE ERROR AND WILL NOT FUNCTION. 10.3 INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior REPLACEMENT OF PARTS 8 716 115 166b (03/2009)
Page 47
Lift up assembly and remove from boiler. NOTE: After re-assembly, check the CO/CO levels as described in the setting of the air/gas ratio section. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior REPLACEMENT OF PARTS 8 716 115 166b (03/2009)
Page 48
IMPORTANT: IF THE JOINT BETWEEN THE AIR/GAS MANIFOLD AND THE HEAT EXCHANGER IS DISTURBED THE SEALING GASKET MUST BE REPLACED. 15.4 15.2 15.3 15.1 INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior REPLACEMENT OF PARTS 8 716 115 166b (03/2009)
Page 49
19.1 Withdraw the spring clip. 19.2 Withdraw the sensor (D) from the housing. To refit, follow the above in reverse. 19.2 19.1 INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior REPLACEMENT OF PARTS 8 716 115 166b (03/2009)
Page 50
23.2 Withdraw the drain tap from its housing To refit, follow the above in reverse. Ensure any seals that have been disturbed are renewed. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior REPLACEMENT OF PARTS 8 716 115 166b (03/2009)
Page 51
25.2 Withdraw the pressure release valve (A) from its housing. To refit, follow the above in reverse. Ensure any seals that have been disturbed are renewed. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior REPLACEMENT OF PARTS 8 716 115 166b (03/2009)
Page 52
27.2 Remove the heat exchanger To refit, follow the above in reverse. Ensure any seals that have been disturbed are renewed. 27.2 INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior REPLACEMENT OF PARTS 8 716 115 166b (03/2009)
Page 53
Gently raise the boiler off the mounting frame. Replace expansion vessel and refit the boiler to the mounting frame. Follow the commissioning procedure in this manual. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior REPLACEMENT OF PARTS 8 716 115 166b (03/2009)
Page 54
Remove manometer and re-seal inlet pressure point on gas valve. Re-assemble and refit boiler case. ‘C’ INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior REPLACEMENT OF PARTS 8 716 115 166b (03/2009)
Remove manometer and re-seal inlet pressure point on gas valve. Re-assemble and refit boiler case. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior REPLACEMENT OF PARTS 8 716 115 166b (03/2009)
S ET TI N G TH E AI R / GAS R ATI O 28kW NG SECTION OF THIS MANUAL. 28kW LPG INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior LPG CONVERSION 8 716 115 166b (03/2009)
FAULT FINDING NOTE : This fault finding information is for guidance only. Worcester cannot be held responsible for costs incurred by persons not deemed to be competent. The electronic control system for this boiler incorporates a blue central indicator. This normally confirms the permanent mains supply but, by flashing at different rates during a fault, provides a guide to the cause as listed.
CENTRAL HEATING FUNCTION INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior CENTRAL HEATING FUNCTION 8 716 115 166b (03/2009)
PREHEAT AND DHW FUNCTION INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior PREHEAT AND DHW FUNCTION 8 716 115 166b (03/2009)
PROTECTION FUNCTION Boiler temperature Run autofroststat below 8°C function Pump run 5 seconds Pump antiseize every 24hrs INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior PROTECTION FUNCTION 8 716 115 166b (03/2009)
Page 64
5. Is the incoming gas pressure at least 18mbar with the boiler at maximum output? Dedicated to heating comfort Worcester, Bosch Group Cotswold Way, Warndon, Worcester WR4 9SW. Tel. 01905 754624 Fax. 01905 754619 Worcester, Bosch Group is a brand name of Bosch Thermotechnology Ltd. www.worcester-bosch.co.uk 8 716 115 166b (03/2009)