Bc10 Basic Controller - Buderus Logamax plus GB162-80 kW Installation Instructions Manual

Condensing gas boiler
Hide thumbs Also See for Logamax plus GB162-80 kW:
Table of Contents

Advertisement

Fig. 45
Electrical wiring diagram
1
81-pole connector (AC 0, 10, 24 and 230 V)
2
16-pole connector (AC 120 V)
3
Connection for pump in connection kit (accessory)
4
Fan
5
Gas valve
6
Transformer
7
Glow ignitor
8
Earth
9
Ionization
10
Pressure sensor
11
Return sensor
12
Safety-temperature sensor
13
Supply sensor
14
Flue gas sensor
15
Fuse (5 amp. FAST, sand filled)
16
BUS function modules
17
Connector for BC10 Basic Controller
18
Room controller RC and EMS bus
19
Outdoor temperature sensor
20
On/off temperature controller (potential free)
21
DHW sensor
22
External switch contact (potential free, e.g. floor heating)
23
External 3-way valve
24
Boiler pump (120 VAC, max. 100 W)
25
DHW pump (pump 120 VAC, max. 100 W)
26
DHW re-circulation pump (pump 120 VAC, max. 100 W)
27
Main power connection 120 V/60 Hz, max. permissible 5 A
28
Mains switch
29
120 VAC function module
30
Ground
IMPORTANT
The wires in this mains lead are colored in accordance
with the following code:
GREEN AND YELLOW - EARTH; BLUE - NEUTRAL;
BROWN - LIVE
As the colors of the wires in the mains lead of the
appliance may not correspond with the colored markings
identifying the terminals in your connector proceed as
follows:
The wire colored green and yellow must be connected to
the terminal on the connector marked with the letter E or
by the earth symbol
or colored green or
green-and-yellow. The wire colored brown must be
connected to the terminal marked with the letter L or
colored red. The wire colored blue must be connected to
the terminal marked with the letter N or colored black.
WARNING
THIS APPLIANCE MUST BE EARTHED
Ensure that your appliance is connected correctly - if you
are in any doubt consult a qualified electrician.
For location of individual components, see service section
and the exploded views in this manual.
Logamax plus GB162- 80/100 kW - Subject to modifications resulting from technical improvements!