Buderus Logamax plus GB162-80 kW Installation Instructions Manual page 59

Condensing gas boiler
Hide thumbs Also See for Logamax plus GB162-80 kW:
Table of Contents

Advertisement

Main
Sub
display
display
Key to display code
code
code
Operating phase:
Communication test while starting up. This display code flashes 5 times
within 5 seconds while starting up to indicate that the communication
between the UBA 3 and the BC10 basic controller is being tested. If a
new UBA 3 or a new KIM was fitted, this code will flash for max. 10
seconds.
Blocking fault:
If this code continues to flash on the display, there is a fault in the
communication between the UBA 3 and the BC10 basic controller.
Any display code with a dot in bottom right hand corner.
Operating phase:
1)
The boiler is in flue gas test or service mode.
Operating phase:
The boiler is in heating mode
1)
Any display code with a blinking dot in bottom right hand corner.
Operating phase:
1)
The boiler is in manual operation mode.
Operating phase:
The boiler is in DHW mode.
1)
Operating phase:
Pump run-over time via the external hot water cylinder 130 seconds at
1)
minimum speed.
The LED "Burner operation" is off.
Operating phase:
The switch optimization program is activated.
This program is activated if there has been a DHW request from an RC
1)
regulator more frequently than once every 10 minutes. This means that
the boiler cannot be restarted until at least 10 minutes have elapsed
since initial burner start-up.
Operating phase:
The boiler cannot start up temporarily after a DHW request has ended.
1)
Pre-operative phase:
The boiler prepares for a burner start-up whenever a heat demand or a
1)
DHW request arises.
Readiness for operation:
The boiler is in standby mode. There is a current heat demand, but too
1)
much energy has been supplied.
Readiness for operation:
The boiler is in standby mode. There is no current heat demand.
1)
Ignition phase:
The gas valve is activated.
1)
Start-up phase:
The boiler starts up after activation of the mains power supply or
1)
completion of a system reset. This code is displayed for a maximum of 4
minutes.
Operating phase:
The flow temperature sensor has detected that the current flow
temperature is higher than the flow temperature setting on the BC10, or
1)
that it is higher than the flow temperature calculated according to the
heating curve, or that it is higher than the flow temperature calculated
for the DHW mode.
Tab. 23 Display codes
Logamax plus GB162- 80/100 kW - Subject to modifications resulting from technical improvements!
Display codes
Display information
Other effects
No heating operation and no DHW.
The room temperature is too high.
The room temperature is not possibly
reached.
The room temperature is not possibly
reached.
13