Dimensions And Connections; Without Pump Group - Buderus Logamax plus GB162-80 kW Installation Instructions Manual

Condensing gas boiler
Hide thumbs Also See for Logamax plus GB162-80 kW:
Table of Contents

Advertisement

4

Dimensions and connections

4
Dimensions and connections
4.1

Without pump group

16.5" (420 mm)
20.5" (520 mm)
Fig. 2
Dimensions and connections without pump
group
A(LA) =Flue gas connection; inside diameter 4" (100 mm)
B(AA) =Air intake connection; inside diameter 4"(100 mm)
C(WB) =Wall Bracket (not shown)
D(VK) =Supply; G1½" union nut with female thread
E(GAS) =Gas connection to boiler; Rp1" female thread
F(RK) =Return; G1½" union nut with female thread
G(AKO) =Condensate outlet; Ø 32 mm (1¼")O/D
10
18.3" (465 mm)
6" (152 mm)
A/B
D/F
G
24.8" (630 mm)
Logamax plus GB162- 80/100 kW - Subject to modifications resulting from technical improvements!
0.25" (6 mm)
0
4.1" (103.5 mm)
E
1.54" (39 mm)
1.4" (35 mm)
5.1" (130 mm)
5.4" (138 mm)
6.4" (162 mm)
The required permanent clearances (closet) are:
in front:
1" (25 mm)
right side:
0
left side:
0
above:
6" (152 mm)
The position selected for installation MUST allow
adequate space for servicing in front of the boiler of at
least 16.5" + 20.5" = 37" (940 mm).
Maintain an installation clearance from combustible
construction from hot water piping of at least 1" (25 mm)
20.5" (520 mm)
0
A
B
C
16" (406 mm)
D
E
F
G
5.1" (130 mm)
5.5" (140 mm