Installation

4XLMF LED Interface Module (MS-4 only)

The 4XLMF supports the RZA-4XF Remote Annunciator module. The wiring of this module must
follow the requirements as specified in "Power-limited Wiring Requirements" on page 24.
Important: The 4XLMF module can only be installed on connectors J3 and J5 of the MS-4 main
circuit board.
4XLB
4XLMF Module
Front View of RZA-4XF
30
+24 VDC
1
Out #1
2
Out #2
3
Out #3
4
Out #4
5
System Trouble
6
Sound
7
Resound
8
Connect to corresponding terminals of
Figure 2.15 4XLMF LED Interface Module
RZA-4XF Remote Annunciator
Note: Make wiring connections with system
power off. Maximum wire impedance is
50 ohms per wiring connection.
Side View
MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011
Installation of Optional Modules