Dip Switch Settings - Fire-Lite MS-2E' MS-4E User Manual

Fire alarm control panel
Table of Contents

Advertisement

Program Options via DIP Switch

3.1 DIP Switch Settings

Switch Number
DIP Switch Number
SW1
SW2
SW3
used to select strobe
synchronization feature as
32
The following tables list the programmable features for the MS-2 and MS-4. Placing a
DIP switch in the ON position will select the feature while placing the DIP switch in the
OFF position will deselect the feature. The exceptions to this rule are SW3 DIP
switches 5 & 6. These two switches are used to select the Notification Appliance
Circuit synchronization feature. A detailed description of each feature is presented in
the following pages.
Important: When any programmable feature is changed by repositioning a DIP switch,
the FACP Reset button must be pressed to ensure that the control panel can read the
new switch position.
Table 3.1 MS-2 DIP Switch Settings
1
Silence Inhibit
2
Auto-silence
3
Temporal Coding
4
Selective Silence (if sync. enabled)
5
Trouble Reminder
6
AC Trouble Delay
7
Autoresettable Supervisory
8
IDC Combination Waterflow/
Supervisory Circuit
1
not used
2
not used
3
IDC1 Verification
4
IDC1 Supervisory
5
IDC2 Verification
6
IDC2 Supervisory
7
not used
8
not used
1
NAC1 Nonsilenceable
2
NAC1 Disable
3
not used
4
not used
No Synchronization
5 & 6
System Sensor Synchronization
shown to the right
Gentex Synchronization
Wheelock Synchronization
7
Nonsilenceable Waterflow for
Combination Circuit
(only if SW1 switch 8 is ON)
8
spare
DIP Switch ON
MS-2/MS-4 PN 51512:D 10/18/04
DIP Switch Settings
Switch 5
Switch 6
OFF
OFF
ON
OFF
OFF
ON
ON
ON