Buderus 600 - 11S Installation And Servicing Instructions page 10

Hide thumbs Also See for 600 - 11S:
Table of Contents

Advertisement

1
Installation
1.3.2
Air supply and flue gas exhaust in a closed
installation
A ventilation cover is integrated into the 600 Series condensing
gas boilers. This cover houses a number of components, such
as the burner and the heat exchanger. Since this ventilation
cover is part of the air supply system, it is vital that it is always
installed correctly.
To ensure optimal operation, the 600 Series appliances must
be connected to a Buderus wall-mounted or roof-mounted flue
terminal. These terminals have been developed specifically for
the 600 Series condensing gas boilers and have been
comprehensively tested. The Buderus wall and roof-mounted
flue terminal kits ensure trouble-free operation.
The following items for the flue (see fig. 2) are included in the
delivery of the boiler:
– pos. 1: 1 Concentric bend 60/100;
– pos. 2: 1 Horizontal flue terminal 60/100;
– pos. 3: 1 Flue finishing kit.
1.3.3
Maximum Flue length
The maximum pipe length of the air supply and flue gas
exhaust pipes for the 600 Series condensing gas boilers (see
table 2) is determined by the total pressure loss of all
components in the flue gas exhaust / air supply system.
Flow pressure available for use [Pa]
11 S
600 Series
35
Take the flue conduit clearances into account when planning
the layout of the place of installation (see subsection 1.3.1:
"Siting the flue terminal" on page 9).
Maximum wall thickness without extensions is 550 mm.
Maintain a minimum side wall clearance of 50 mm (see fig. 3).
1.3.4
Additional flue parts
Additional flue parts (see table 3) can be ordered from your
supplier.
Subject to modifications resulting from technical improvements!
10
Installation and maintenance instructions for wall-mounted condensing gas boiler 600 - 11S/19S/24S/24C • 05/2004
19 S
24 S
24 C
60
100
10
1
Fig. 2
Horizontal flue pack
Fig. 3
Side flue and rear flue installation
Maximum
Boiler
pipe length
600 Series
L = 7.5 m
Table 2
Pipe length
Flue parts
Concentric pipe, 500 mm long, adjustable
Concentric pipe, 1000 mm long, not adjustable
Concentric bend 90°
Concentric bend 45°
Table 3
Additional flue parts
Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
2
3
L
550 mm
50 mm
For every 90° bend the
maximum pipe length has
to be reduced by
1.2 m
Order No.
NE 83703
NE 83704
NE 83705
NE 83706