Mitsubishi Electric FR-A720-0.4K Instruction Manual page 327

Fr-a700 series
Hide thumbs Also See for FR-A720-0.4K:
Table of Contents

Advertisement

Selection of operation mode and operation location
(4) External operation mode (setting "0" (initial value), "2")
3
Forward rotation start
Reverse rotation start
Switch
Frequency setting
potentiometer
Potentiometer
(5) PU operation mode (setting "1")
Operation panel
(FR-DU07)
316
5 6
4
7
8
9
10
Inverter
STF
STR
SD
10
2
5
⋅ Select the External operation mode when the start
command and the frequency command are applied
from a frequency setting potentiometer, start switch, etc.
externally and connecting them to the control circuit
terminals of the inverter.
⋅ Generally, parameter change cannot be performed with
the operation panel in the External operation mode.
(Some parameters can be changed. Refer to the
detailed description of each parameter.)
⋅ When "0" or "2" is selected for Pr. 79, the inverter enters
the External operation mode at power ON. (When using
the Network operation mode, refer to page 321)
⋅ When parameter changing is seldom necessary, setting
"2" fixes the operation mode to External operation
mode.
When
frequent
necessary, setting "0" (initial value) allows the operation
mode to be changed easily to PU operation mode by
pressing
of the operation panel. When you
switched to PU operation mode, always return to
External operation mode.
⋅ The STF and STR signal are used as a start command,
and the voltage or current signal to terminal 2, 4,
multispeed signal, JOG signal, etc. are used as
frequency command.
⋅ Select the PU operation mode when performing
operation by only the key operation of the operation
panel (FR-DU07) or parameter unit (FR-PU04/FR-
PU07). Also select the PU operation mode when
making communication using the PU connector.
⋅ When "1" is selected for Pr. 79, the inverter enters the
PU operation mode at power ON. You cannot change to
the other operation mode.
⋅ The setting dial of the operation panel can be used for
setting like a potentiometer. (Pr. 161 Frequency setting/key
lock operation selection, refer to page 393.)
⋅ When PU operation mode is selected, the PU operation
mode signal (PU) can be output.
For the terminal used for the PU signal output, assign
the function by setting "10 (positive logic) or 110
(negative logic)" in any of Pr. 190 to Pr. 196 (output
terminal function selection).
parameter
changing
is

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents