Mitsubishi Electric FR-A720-0.4K Instruction Manual page 300

Fr-a700 series
Hide thumbs Also See for FR-A720-0.4K:
Table of Contents

Advertisement

Forward
STF
rotation
AU
SD
4 to 20mADC
Current
4
Frequency
input
setting
5
equipment
Connection diagram using
terminal 4 (4 to 20mADC)
Forward
STF
rotation
SD
4 to 20mADC
Current
2
Frequency
input
setting
equipment
5
Connection diagram using
terminal 2 (4 to 20mADC)
Reverse
Set frequency
Forward
(Hz)
rotation
rotation
60
Reversible
Not reversible
-5
0
Terminal 1 input (V)
(-10)
Compensation input characteristic
when STF is on
♦ Parameters referred to ♦
Pr. 22 Stall prevention operation level
Pr. 125 Terminal 2 frequency setting gain frequency, Pr. 126 Terminal 4 frequency setting gain frequency
Pr. 252, Pr. 253 Override bias/gain
Pr. 858 Terminal 4 function assignment, Pr. 868 Terminal 1 function assignment
(3) Perform operation by analog input current
Inverter
⋅ When the pressure or temperature is controlled constant by a fan, pump,
etc., automatic operation can be performed by inputting the output signal
Voltage/current
input switch
0 to 20mADC of the adjuster to across the terminals 4 and 5.
⋅ The AU signal must be turned ON to use the terminal 4.
⋅ Setting any of "6, 7, 16, 17" in Pr. 73 and a voltage/current input switch in
Inverter
the ON position changes the terminal 2 to the current input specification.
Voltage/current
At this time, the AU signal need not be turned ON.
input switch
4
2
(4) Perform forward/reverse rotation by analog input
(polarity reversible operation)
⋅ Setting any of "10 to 17" in Pr. 73 enables polarity reversible operation.
⋅ Providing ± input (0 to ±5V or 0 to ±10V) to the terminal 1 enables
forward/reverse rotation operation according to the polarity.
+5
(+10)
Refer to page 152
Refer to page 290
Frequency/torque setting by analog
input (terminal 1, 2, 4)
Refer to page 294
Refer to page 285
4
289