Mitsubishi Electric FR-A720-0.4K Instruction Manual page 221

Fr-a700 series
Hide thumbs Also See for FR-A720-0.4K:
Table of Contents

Advertisement

Motor brake and stop operation
(7) DC feeding mode 2 (Pr. 30 = "20, 21")
⋅ When "20 or 21" is set in Pr. 30, operation is performed with AC power supply normally and with DC power supply
such as battery at power failure.
⋅ Connect the AC power supply to terminal R/L1, S/L2, and T/L3 and connect the DC power supply to terminal P/+
and N/-. Also, remove jumpers across terminal R/L1 and R1/L11 as well as S/L2 and S1/L21, and connect
terminals R1/L11 and S1/L21 to terminal P/+ and N/-.
⋅ Turning ON the DC feeding operation permission signal (X70) enables DC power supply operation. Refer to the
table below for I/O signals.
signal
DC feeding operation
X70
permission signal
Input
X71
DC feeding cancel signal
Output Y85
DC feeding signal
⋅ The following shows the connection diagram when switching to a DC power using inverter power failure detection.
Three-phase AC
power supply
DC feeding permission signal
Frequency command
Frequency setting
*1
Assign the function using Pr. 178 to Pr. 189 (input terminal function selection).
*2
Assign the function using Pr. 190 to Pr. 196 (output terminal function selection).
210
Name
When performing operation with DC feeding, turn
ON the X70 signal.
When the inverter output is shut off because of
power failure, the inverter starts about 150ms
after switching ON X70 signal. (When automatic
restart operation is valid, the inverter starts after
additional Pr. 57 set time has elapsed.)
When the X70 signal turns OFF during inverter
operation, output is shutoff (Pr .261 = 0) or the
inverter is decelerated to a stop (Pr. 261 ≠ 0).
Turn this signal ON to stop DC feeding.
When the X71 signal is turned ON during inverter
operation with turning ON the X70 signal, output
is shutoff (Pr. 261 = 0) or the inverter is
decelerated to a stop (Pr. 261 ≠ 0), then the X85
signal turns OFF after the inverter stop.
After turning ON the X71 signal, operation cannot
be performed even if the X70 signal is turned ON.
This signal turns ON during power failure or under
voltage of AC power.
The signal turns OFF when the X71 signal turns
ON or power is restored.
The Y85 signal does not turn OFF during inverter
operation even if the power is restored and turns
OFF after an inverter stop.
When the Y85 signal turns ON because of
undervoltage, the Y85 signal does not turn OFF
even if undervoltage is eliminated.
ON/OFF status is retained at an inverter reset.
MCCB
MC
DC power
MC1
(+)
(-)
Forward rotation start
Reverse rotation start
DC feeding cancel signal
Contact input common
3
2
potentiometer
1
1/2W1kΩ
Description
Inverter
Inrush
R/L1
current
U
limit circuit
S/L2
V
W
T/L3
R1/L11
S1/L21
P/+
N/-
STF
STR
*1
X70
DC feeding signal
*1
X71
*2
Y85
SD
10
SE
2
5
Parameter Setting
Set 70 in any of Pr. 178 to Pr. 189.
Set 71 in any of Pr. 178 to Pr. 189.
Set "85 (positive logic) or 185
(negative logic)" in any of Pr. 190
to Pr. 196
IM
Earth
(Ground)
MC1