Mitsubishi Electric FR-A720-0.4K Instruction Manual page 244

Fr-a700 series
Hide thumbs Also See for FR-A720-0.4K:
Table of Contents

Advertisement

Signal
Setting
Name
69
CLR
Simple position droop pulse clear (for FR-A7AP/FR-A7AL)
70
X70
DC feeding operation permission
71
X71
DC feeding cancel
74
X74
Magnetic flux decay output shutoff signal
Proximity dog (assigned to JOG terminal (Pr. 185) only) (for FR-
76
X76
A7NS)
*6
83
X83
0V calibration request (for FR-A7AD)
9999
No function
*1
When Pr. 59 Remote function selection = "1 or 2", the functions of the RL, RM and RH signals change as listed above.
*2
When Pr. 270 Stop-on contact/load torque high-speed frequency control selection = "1, 3, 11 or 13", the functions of the RL and RM signals change as listed
above.
*3
The OH signal turns ON when the relay contact "opens".
*4
The FR-A7AX (16-bit digital input) is needed to externally input a stop position under orientation control.
*5
Servo ON is valid during position control under vector control operation.
*6
Available only when the plug-in option is mounted. For details, refer to the instruction manuals of each plug-in options.
REMARKS
⋅ Same function can be assigned to two or more terminals. In this case, the logic of terminal input is OR.
⋅ The priorities of the speed commands are in order of JOG > multi-speed setting (RH, RM, RL, REX) > PID (X14).
⋅ When the X10 signal (FR-HC, MT-HC, FR-CV connection - inverter operation enable signal) is not set or when the PU
operation external interlock (X12) signal is not assigned at the Pr. 79 Operation mode selection setting of "7", the MRS signal
shares this function.
⋅ Same signal is used to assign multi-speeds (7 speeds) and remote setting. They cannot be set individually.
(Same signal is used since multi-speed (7 speeds) setting and remote setting are not used to set speed at the same time.)
⋅ When V/F switching (X18) signal and load pattern selection forward/reverse rotation boost (X17) signal are not assigned, the
RT signal shares this function. (Pr. 81 Number of motor poles = "12, 14, 16, 18, 20")
In this case, V/F control is controlled by the second function.
CAUTION
⋅ Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Also
check that wiring is correct, since the terminal name and the signal function became different. Set parameters after confirming
the function of each terminal.
(2) Response time of each signal
⋅ The response time of the X10 signal is within 2ms. However, when the X10 signal is not assigned at the Pr. 30
Regenerative function selection setting of "2" (FR-HC, MT-HC/FR-CV connection), the response time of the MRS
signal is within 2ms.
Pr. 17 MRS input selection is invalid.
Pr. 30
MRS
Setting
Assignment
×
2
×
Other than 2
Function
*6
Response Time
X10
Assignment
MRS
×
Within 2ms
Within 20ms
×
Within 20ms
Within 20ms
Function assignment of external terminal and control
Related Parameters
Pr. 291, Pr. 419 to Pr. 430, Pr. 464
*6
Pr. 30, Pr. 70
Pr. 30, Pr. 70
Pr. 17
X10
Invalid
Within 2ms
Within 2ms
Valid
Valid
Valid
Refer to
Page
137
207
207
238
4
233

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents