(3) Set multiple electronic thermal relay functions (Pr. 51)
Use this function when rotating two motors of different rated currents individually by a
single inverter. (When rotating two motors together, use external thermal relays.)
⋅ Set the rated current of the second motor in Pr. 51.
⋅ When the RT signal is ON, thermal protection is provided based on the Pr. 51 setting.
Pr. 450
Pr. 9
Second applied
Electronic thermal
motor
O/L relay
9999
0
Other than
9999
0
Other than
0
9999
Other than
Other than
9999
0
.... Output current value is used to perform integration processing.
.... Output current is assumed as 0A to perform integration processing. (cooling processing)
×
..... Electronic thermal relay function is not activated.
REMARKS
⋅ The RT signal acts as the second function selection signal and makes the other second functions valid. (Refer to page 235)
⋅ The RT signal is assigned to the RT terminal in the initial setting. By setting "3" in any of Pr. 178 to Pr. 189 (input terminal function
selection), you can assign the RT signal to the other terminal.
(4) Electronic thermal relay function pre-alarm (TH) and alarm signal (THP signal)
100%: Electronic thermal relay function alarm operation value
Electronic thermal
relay function
operation level
Electronic thermal O/L
(THP)
relay alarm
OFF
CAUTION
⋅ Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection) may affect the other functions. Set
parameters after confirming the function of each terminal.
RT = OFF
Pr. 51
First
Second electronic thermal O/L
relay
motor
×
9999
0
×
×
0.01 to 500 (0.1 to 3600)
9999
0
0.01 to 500 (0.1 to 3600)
9999
×
×
0
×
0.01 to 500 (0.1 to 3600)
9999
0
0.01 to 500 (0.1 to 3600)
⋅ The alarm signal (THP) is output and an electronic thermal pre-
alarm (TH) is displayed when the electronic thermal relay
100%
function cumulative value reaches 85% of the level set in Pr. 9
85%
or Pr. 51. If it reaches 100% of the Pr. 9 Electronic thermal O/L
relay setting, electronic thermal relay function protection (E.
THM/E.THT) occurs.
⋅ The inverter does not trip if the alarm signal is output.
ON
ON
Time
⋅ For the terminal used for the THP signal output, assign the
function by setting "8" (positive logic) or "108" (negative logic) in
any of Pr. 190 to Pr. 196 (output terminal function selection).
Selection and protection of a motor
RT = ON
Second
First
Second
motor
motor
motor
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
MC
IM
MC
U
V
IM
W
RT
SD
185