Troubleshooting for RA Indoor Unit
Troubleshooting
Check No.06
Refer to P.331
324
Be sure to turn off power switch before connect or disconnect connector, or parts
damage may be occurred.
Caution
Check the air passage.
Is there any
short-circuit?
NO
Check the intake air filter.
NO
Is it very dirty?
Check the dust accumulation on
the indoor unit heat exchanger.
Is it very dirty?
NO
Check No. 06
Indoor unit heat exchanger
thermistor check
Does it conform to the
thermistor characteristic
chart?
NO
YES
YES
YES
YES
SiEN18-622
Provide sufficient air passage.
Clean the air filter.
Clean the heat exchanger.
Replace the indoor unit PCB.
Replace the thermistor
(replace the indoor unit PCB).
(R4695)
Troubleshooting