Daikin Super Multi Plus E-Series Service Manual page 188

Super multi plus e-series
Hide thumbs Also See for Super Multi Plus E-Series:
Table of Contents

Advertisement

SiEN18-622
4.5.5 Fan Speed Changeover When Thermostat is OFF
By setting to "Set Fan Speed," you can switch the fan speed to the set fan speed when the
heating thermostat is OFF.
∗ Since there is concern about draft if using "fan speed up when thermostat is OFF," you should
take the setup location into consideration.
Setting Table
4.5.6 Wireless Setting (Address and MAIN/SUB Setting)
Explanation
If several infrared remote control units are used together in the same room (including the case
where both group control and individual remote control control are used together), be sure to set
the addresses for the receiver and infrared remote control. (For group control, see the attached
installation manual for the indoor unit.) If using together with a wired remote control, you have to
change the main/sub setting or the receiver.
Receiver Setting
Set the wireless address switch (SS2) on the transmitter board according to the table below.
Wireless Address
Switch (SS2)
When using both a wired and a infrared remote control for 1 indoor unit, the wired controller
should be set to MAIN. Therefore, set the MAIN/SUB switch (SS1) of the transmitter board to
SUB.
MAIN/SUB Switch
(SS1)
After completing setting, seal off the opening of the address switch and the MAIN/SUB switch
with the attached sealing pad.
Test Operation
Mode No.
First Code No.
12(22)
Unit No.
Second Code No.
3
01
02
No.1
No.2
MAIN
SUB
(S1940)
Field Setting for SkyAir Indoor Unit
Setting
LL Fan Speed
Set Fan Speed
No.3
175