I N S TA L L E R ’ S I N S TA L L AT I O N I N S T R U C T I O N S
1)
Turn on the gas and water.
2)
Check for water and gas leaks. Use soapy water to test for gas leaks.
3)
Remove pressure test point screw, attach pressure gauge to test point.
4)
Turn Power on.
5)
Open any hot water tap fully.
6)
Check test point or supply pressure in water columns per inch.
Manifold Pressure:
Natural Gas
LPG
NOTE: The pressure may be low due to too little flow, too high an incoming temperature,
and/or undersized gas piping. Examine these areas before determining that the
pressure needs to be adjusted. Contact Rinnai before adjusting manifold
pressures at 1-800-621-9419. Failure to contact Rinnai, could void unit’s
warranty.
7)
If it is determined that the gas pressure needs adjusting, first check the in
coming pressure at the test point on the gas inlet. If it is correct follow the
adjusting procedure contained in the pouch of the unit EXACTLY. If in doubt
call Rinnai 1-800-621-9419.
The regulator is pre-set at the factory, it should not need resetting.
8)
Turn the hot water off. Turn the power off. Remove the pressure guage and
replace the test point screw. Check for a gas leak around the test point
screw.
9)
Replace the front cover.
10) Turn the power back on.
11) Check the operation of the unit. Check the operation of each of the remote
controls. Check the operation of the Power failure protection system.
12) Explain the proper operation of the Integrity V2532C to the customer.
www.rinnai.us
3.7" Hi. fire
0.77" Lo. fire
4.2" Hi. fire
0.93" Lo. fire
Testing
Supply pressure:
Natural Gas
LPG
3 6
Min. 7" Max. 10.5"
Min. 10"
Max. 13.5"
Model V2532FFUC