Rinnai V75i series Installation And Operation Manual

Rinnai V75i series Installation And Operation Manual

Direct vent tankless water heater
Hide thumbs Also See for V75i series:
Table of Contents

Advertisement

Available languages

Available languages

FOR INDOOR APPLICATIONS ONLY
V75i ....................... REU-VC2528FFU-US
V65i ....................... REU-VC2025FFU-US
FOR OUTDOOR APPLICATIONS ONLY
V75e ...................... REU-VC2528W-US
V65e ...................... REU-VC2025W-US
READ ALL OF THE INSTRUCTIONS THOROUGHLY BEFORE INSTALLING OR OPERATING THIS WATER HEATER.
This manual provides information on the installation, operation, and maintenance of the water heater. For proper
operation and safety, it is important to follow the instructions and adhere to the safety precautions.
A licensed professional must install the water heater according to the exact instructions on pages 4-27.
The consumer must read the entire manual to properly operate the water heater and to have regular maintenance
performed.
WARNING
— Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other
appliance.
— WHAT TO DO IF YOU SMELL GAS
 Do not try to light any appliance.
 Do not touch any electrical switch; do not use any phone in your building.
 Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
 If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a licensed professional.
This entire manual must be left for the consumer. The consumer must read and
refer to this manual for proper operation and to maintain the water heater.
ANS Z21.10.3 ● CSA 4.3
If the information in these instructions is not followed exactly, a fire or explosion
may result causing property damage, personal injury or death.
Direct Vent Tankless Water Heater
Installation and Operation Manual

Advertisement

Table of Contents
loading

Summary of Contents for Rinnai V75i series

  • Page 1 Direct Vent Tankless Water Heater Installation and Operation Manual FOR INDOOR APPLICATIONS ONLY V75i ....... REU-VC2528FFU-US V65i ....... REU-VC2025FFU-US FOR OUTDOOR APPLICATIONS ONLY V75e ...... REU-VC2528W-US V65e ...... REU-VC2025W-US ANS Z21.10.3 ● CSA 4.3 READ ALL OF THE INSTRUCTIONS THOROUGHLY BEFORE INSTALLING OR OPERATING THIS WATER HEATER. This manual provides information on the installation, operation, and maintenance of the water heater.
  • Page 2: Table Of Contents

    If you have any questions or feel that the manual is incomplete contact Rinnai at 1-800-621-9419 Important Safety Information Safety Definitions This is the safety alert symbol.
  • Page 3: Safety Behaviors And Practices For The Consumer And Installer

    Safety Behaviors and Practices for the Consumer and Installer WARNING   Before operating, smell all around the appliance Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not area for gas.
  • Page 4: Installation Instructions

    Installation Instructions Installer Qualifications General Instructions A licensed professional must install the appliance, DO NOT inspect it, and leak test it before use. The warranty  Do not install the V75i or the V65i outdoors. will be voided due to improper installation. ...
  • Page 5: Prepare For Installation

    Prepare for installation  The appliance must be isolated from the gas supply Parts included piping system by closing its individual manual shutoff valve during any pressure testing of the gas  Tankless water heater supply piping system at test pressures equal to or ...
  • Page 6: Determine Installation Location

     Install as far away as possible from air inlet Rinnai provides a “Scale Control System” that offers vents. Corrosive fumes may be released through superior lime scale prevention and corrosion control...
  • Page 7: Vent Termination Clearances

    Vent Termination Clearances For indoor models, you must install a vent termination to bring in combustion air and expel exhaust. TERMINATION INSIDE CORNER DETAIL Clearance in Ref. A also applies to anticipated snow line SNOW FIXED CLOSED OPERABLE FIXED AIR SUPPLY INLET CLOSED OPERABLE VENT TERMINAL...
  • Page 8 Additional clearances - V75i, V65i 60" (1.52 m) Check on whether local codes supersede these clearances. between  terminals at Avoid termination locations near a dryer vent. different levels  Avoid termination locations near commercial cooking exhaust.  You must install a vent termination at least 12 inches from the ground Important considerations for locating vent termination under a soffit (ventilated or unventilated...
  • Page 9: Additional Clearances

    Additional clearances V75e, V65e Local codes supersede these clearances.  Avoid termination locations near a dryer vent.  Avoid termination locations near commercial cooking exhaust. (50 mm) between terminals at same level (0.91 m) to ventilated or unventilated 36" soffit or eve vent; or to a deck or porch 12"...
  • Page 10 Unit clearances Indoor models: V75i, V65i Outdoor models: V75e, V65e to Non- to Non- to Combustibles to Combustibles Combustibles Combustibles inches (mm) inches (mm) inches (mm) inches (mm) Top of Heater 6 * (152) 2 *(51) Top of Heater 12 (305) 2 (51) Back of Heater 0 (zero)
  • Page 11: Maximum Vent Length

    Maximum vent length Freeze Protection (indoor models only) Make sure that in case of freezing weather that the water heater and its water lines are protected to 1. Determine the number of 90 degree elbows in prevent freezing. Damage due to freezing is not the vent system.
  • Page 12: Checklist To Determine Installation Location

    Mount to Wall Checklist to Determine Installation Location □ The water heater is not exposed to corrosive compounds in the air. □ The water heater location complies with the wall installation clearances. brackets □ For indoor models, the planned venting will not exceed the maximum length for the number of elbows used.
  • Page 13: Installation Of Venting (Indoor Models Only)

    If it becomes necessary to access an enclosed vent therefore is certified and listed with the vent system for service or repairs, Rinnai is not responsible system. You must use vent components that are for any costs or difficulties in accessing the vent certified and listed with the water heater model.
  • Page 14 Flue Installation (indoor models only) Install the venting termination according to the diagrams and instructions below. Horizontal Termination without using the Condensate Collector WARNING * The condensate collector must be used in horizontal terminations if a vertical rise in If the condensate collector is not used, the drain pipe the vent system exceeds 5ft.
  • Page 15: Condensate (Indoor Models Only)

    Condensate (indoor models only) INFORMATION Condensate formation can occur in high efficiency direct vent appliances. Without proper drainage  A condensate trap is available, P/N 222053. condensate will damage the heat exchanger.  Regions of cold climate will create more To prevent condensate damage follow these condensate in the vent system.
  • Page 16: Installation Of Plumbing

    The relief line should allow for complete Isolation Valves drainage of the valve and the line. Rinnai strongly recommends the installation of  Do not place any other type valve or shut off isolation valves on the cold and hot water lines...
  • Page 17: Piping Diagram For Basic Installation

    Piping Diagram for Basic Installation Rinnai Water Heater Rinnai Equipment List Rinnai Water Heaters RIK-KIT (Optional) (3/4" Fittings Include: 2 Unions, 2 Ball Valves, 2 Drain Valves and 1 Pressure Relief Valve.) 3/4" Hot Water Supply Line For Building Fixtures This is not an engineered drawing.
  • Page 18: Checklist For Plumbing

    □ Check for proper water pressure to the water corrosive.) heater. Minimum water pressure is 50 psi. Rinnai  Use approved connectors to connect the unit to recommends 60-80 psi for maximum the gas line.
  • Page 19  Any compound used on the threaded joint of the Pipe Sizing Table - Natural Gas gas piping shall be a type which resists the action Schedule 40 Metallic Pipe of liquefied petroleum gas (propane / LPG). Inlet Pressure: less than 2 psi (55 inches W.C.) ...
  • Page 20: Connect Electricity

    Connect Electricity Adjust for High Altitude WARNING Using the SW1 DIP switch (tan switches), set switches 2 and 3 to the values shown in table below for your Do not use an extension cord or an adapter plug with altitude. The default setting for the appliance is 0- this appliance.
  • Page 21: Installation Of Temperature Controller

    Controllers cannot be wired in series. connections inside the unit. Do not connect the temperature controller to the Maximum 4 Controllers Rinnai 120VAC terminals provided for the optional solenoid Water drain valves. Heater Indoor models have their controller built into the front panel.
  • Page 22: Mounting The Controller

    Mounting the controller 1. Make three holes in the wall as shown. Outline of Remote securing screw 1-21/32" wiring hole 3-5/16" securing screw 2. Run the cable between the controller and the water heater or the controller and another controller. 3.
  • Page 23: Final Checklist

    □ Final Checklist A manual gas control valve has been placed in the gas line to the water heater. □ The water heater is not subject to corrosive □ Check the gas lines and connections for leaks. compounds in the air. □...
  • Page 24: Technical Data

    Technical Data Specifications V75i V65i V75e V65e Minimum Gas Consumption Btu/h 10,300 Maximum Gas Consumption Btu/h 180,000 150,000 180,000 150,000 0.26 - 7.5 GPM 0.26 - 6.6 GPM 0.26 - 7.5 GPM 0.26 - 6.6 GPM Hot water capacity (Min - Max) * (1.0 - 28.5 L/min) (1.0 - 25.0 L/min) (1.0 - 28.5 L/min)
  • Page 25: Dimensions

    Dimensions Inches (millimeters) V75i, V65i 9.27 (235.5) 14.04 (356.6) 0.4~1.8(10~45) Variable 5.05 (128.1) DIMENSION Inches (mm) DIMENSION Inches (mm) A (GAS) 1.31 (33.2) 4.33 (110) A (COLD) 1.93 (49) 2.89 (73.3) A (HOT) 1.35 (34.4) 1.85 (47) 4.21 (106.9) 3.44 (87.3) 1.17 (29.8) V75e, V65e 9.27 (235.5)
  • Page 26: Pressure Drop And Water Flow Curves

    Pressure Drop Curve V65i/e V75i/e 60.00 55.00 50.00 45.00 40.00 35.00 30.00 25.00 20.00 15.00 10.00 5.00 0.00 Water Flow (gpm) Water Flow Curve 10.0 V75i/e V65i/e delta T - Temperature Rise (°F) Value Series Manual...
  • Page 27: Ladder Diagram

    Ladder Diagram Value Series Manual...
  • Page 28: Operation Instructions

    V65e ..... REU-VC2025W-US Important Facts about your Water Heater Thank you for purchasing a Rinnai Tankless Water Heater. For proper operation and safety, it is important to follow the instructions and adhere to the safety precautions. Read all of the instructions and the warranty thoroughly before operating this water heater. Keep this manual in a safe place.
  • Page 29: Consumer Operation Guidelines For The Safe Operation Of Your Water Heater

    Consumer Operation Guidelines for the Safe Operation of your Water Heater FOR YOUR SAFETY READ BEFORE OPERATING WARNING If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. A.
  • Page 30: How To Use The Temperature Controller

    -up the water must be treated and/or the heat on the floor. exchanger flushed regularly. Rinnai provides a “Scale Control System” that offers superior lime  Keep the area around the appliance clear and free...
  • Page 31: How To Set The Temperature

    How to Set the Temperature This water heater requires a minimum flow rate to operate. This rate can be found on the specification page in this manual. In some cases when you are not getting hot water or if the water alternates between hot and cold, it is due to the water flow being below or close to the minimum flow rate.
  • Page 32: Temperature Options Without A Temperature Controller

    Water temperatures over 125° F (52°C) can cause severe burns or scalding. Refer to the Danger Alert on water temperatures. Rinnai shall not, in any event, be liable for damages resulting from such misuse or misapplication.
  • Page 33: Diagnostic Codes

    Diagnostic Codes This water heater is designed to display diagnostic codes. If there is a potential operation concern refer to the code and remedy on the next page. To Display Diagnostic Information To display the most recent diagnostic codes press and hold the “On/Off” button for 2 seconds on the MC-91-2 controller.
  • Page 34: Diagnostic Codes And Remedies

    Diagnostic Codes and Remedies WARNING Some of the checks below should be done by a licensed professional. Consumers should never attempt any action that they are not qualified to perform. Code Definition Remedy Power interruption during Bath Fill (Water will not flow when Turn off all hot water taps.
  • Page 35 LC2,…) Off button on the temperature controller 5 times. Repeated LC codes will eventually lockout “LC”) the water heater. Please call Rinnai technical department. Maintenance has been Indicates a licensed professional performed maintenance or corrected an issue. performed Clean inlet water supply filter.
  • Page 36: Required Maintenance

    Required Maintenance The appliance must be inspected annually by a licensed professional. Repairs and maintenance should be per- formed by a licensed professional. The licensed professional must verify proper operation after servicing. WARNING To protect yourself from harm, before performing maintenance: ...
  • Page 37: Pressure Relief Valve

    WARNING Freeze Protection Make sure that in case of freezing weather that the Testing the pressure relief valve should only be water heater and its water lines are adequately performed by a licensed professional. Scalding hot protected to prevent freezing. Damage due to water may be released under pressure.
  • Page 38: Flushing The Heat Exchanger

    An LC0~LC9 or “00” diagnostic code indicates the unit is beginning to lime up and must be flushed. Failure to flush the appliance will cause damage to the heat exchanger. Damage caused by lime build-up is not covered by the unit’s warranty. Rinnai strongly recommends installation of isolation valves to allow for flushing of the heat exchanger.
  • Page 39: Manual Draining Of The Water Heater

    Manual Draining of the Water Heater WARNING To avoid burns, wait until the equipment cools down before draining the water. The water in the appliance will remain hot after it is turned off. If the water heater is not going to be used during a period of possible freezing weather, it is recommended that the water inside the water heater be drained.
  • Page 40: State Regulations

    State Regulations NOTICE BEFORE INSTALLATION This direct-vent appliance must be installed by a licensed professional. If you are not properly trained, you must not install this unit. IMPORTANT: In the State of Massachusetts (248 CMR 4.00 & 5.00) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:...
  • Page 41: Replacement Parts

    Replacement Parts The Technical Sheet which is located inside the front cover of the water heater contains a complete illustrated parts list. Tech Sheet Gas Control Assembly Electrode / Flame Rod Item No. Gas Control Assembly Electrode / Flame Rod Kit 116, 117 Fan Assembly / Motor Heat Exchanger...
  • Page 42: Limited Warranty

    Rinnai will replace the product with a comparable product at Rinnai’s discretion. If a component or product returned to Rinnai is found to be free of defects in material or workmanship, or damaged by improper installation or damaged during return shipping, the warranty claim for product, parts and labor may be denied.
  • Page 43 Refer to the Water Quality Section in the Operation and Installation Manual. Limitation on warranties No one is authorized to make any other warranties on behalf of Rinnai America Corporation. Except as expressly provided herein, there are no other warranties, expressed or implied, including, but not limited to warranties of...
  • Page 44: French Version

    Chauffe-eau d’intérieur sans réservoir à ventilation directe Manuel d'installation et d'utilisation POUR LES APPLICATIONS INTÉRIEURES SEULEMENT V75i....... REU-VC2528FFU-US V65i....... REU-VC2025FFU-US POUR LES APPLICATIONS EXTÉRIEUR SEULEMENT V75e ...... REU-VC2528W-US V65e ...... REU-VC2025W-US ANS Z21.10.3 ● CSA 4.3 LIRE TOUTES LES INSTRUCTIONS SOIGNEUSEMENT AVANT D’INSTALLER OU D’EXPLOITATION DE CETTE CHAUFFE-EAU.
  • Page 45 Nous allons cependant continuer à vous contacter avec les informations pertinentes pour le produit vous inscrit ou vous rendre compte avec nous. Si vous avez des questions ou se sentent que le manuel est incomplète, veuillez communiquer avec Rinnai au 1-800-621-9419.
  • Page 46: Les Pratiques Et Les Comportements De Sécurité Pour Les Consommateurs Et Les Installateurs

    Les pratiques et les comportements de sécurité pour les consommateurs et les installateurs AVERTISSEMENT   Utilisez seulement votre main pour pousser ou Avant d'exploitation, une odeur tout autour de la tourner le bouton de contrôle des gaz. Ne jamais zone de l'appliance pour le gaz.
  • Page 47: Installation D'instructions

    Installation d’instructions Qualifications d'installateur Instructions générales Un professionnel agréé doit installer l'appareil, NE FAITES PAS inspecter et fuite de le tester avant des utiliser. La  Le V75i et V65i n'est pas prévu pour une garantie sera être annulée en raison de la mauvaise installation à...
  • Page 48: Préparez-Vous À L'installation

    Préparez-vous à l'installation  L'appareil et sa vanne de gaz doivent être Pièces incluses débranchés de la conduite d'alimentation en gaz durant les essais du système en pression dépassant  Chauffe-eau sans Réservoir 1/2 psi (3.5 kPa ou 13,84 pouces de hauteur de ...
  • Page 49: Déterminez L'endroit D'installation

    Installez le chauffe-eau aussi loin que possible des par l'eau dure définie à haute température. hottes de ventilation d'échappement. Un kit de traitement de l'eau est disponible depuis Rinnai. Ce kit  Installez aussi loin que possible des bouches d'air fournit un contrôle de la prévention et à...
  • Page 50 Espacements pour terminaison de cheminée (ANS Z21.10.3, CSA 4.3) Vous devez installer une fin de vent à TERMINATION DÉTAIL D'ANGLE INSIDE Terminaison INTÉRIEUR COR NER DETAIL apporter dans l'air de combustion et d'expulser des gaz d'échappement. Clearance in Dédouanement en Ref.
  • Page 51 Dégagements additionnels V75e, V65e Vérifier si les codes locaux remplacent ces habilitations.  Éviter les endroits de résiliation près d'un évent sécheur.  Évitez les endroits de résiliation près d'échappement (50 mm) entre cuisson commercial. (0.91 m) à évent  terminaux au soffite ou eve ventilé...
  • Page 52 Dégagements d'unité Vers le haut Vers le haut Sur le côté Sur le côté Vers l'avant Vers l'avant Vers le sol Vers le sol Modèles d'intérieur: V75i, V65i Modèles extérieurs: V75e, V65e Jusqu'à Jusqu'à Jusqu'à Jusqu'à matières matières matières matières non- non- combustibles...
  • Page 53 Longueur maximum de ventilation Protection de gel 1. Déterminez le nombre de coudes à 90° dans le Assurez-vous que dans le cas de congélation météo système de ventilation (deux coudes à 45° que le chauffe-eau et ses lignes de l'eau sont protégés comptent pour un coude à...
  • Page 54: Liste De Vérification Pour Déterminez

    Bâti à murer Liste de vérification pour déterminer l'endroit d’installation □ Le chauffage de l'eau n'est pas corrosifs composés dans l'air. □ L'emplacement de chauffage de l'eau est parenthèses conforme avec les dégagements. d'installation de □ (Modèles d'intérieur) La ventilation prévue ne dépassera pas la longueur maximale pour le nombre de coudes utilisé.
  • Page 55: Installation De La Mise À L'air Libre (Modèles D'intérieur)

    S'il devient nécessaire d'accéder à un système d'évacuation le vent du fabricant. fermée pour le service ou les réparations, Rinnai n'est pas  responsable des frais ou des difficultés à accéder au Vent horizontal de soutien s'exécute tous les système de ventilation.
  • Page 56 Installation de conduit de cheminée (modèles d'intérieur) Résiliation horizontale sans utiliser le collecteur de condensat * Un collecteur de condensat est requis sur les AVERTISSEMENT terminaisons horizontales si une élévation verticale dans le système de ventilation Si un collecteur de condensat n'est pas utilisé, le tuyau dépasse 5' (1,5 m).
  • Page 57: Condensat (Modèles D'intérieur)

    Condensat (modèles d'intérieur) L’INFORMATION La formation de condensat peut arriver même sur les appareils à ventilation directe de haute performance.  Un collecteur de condensat intégré. Pour éviter que le condensat n'endommage, suivez  Dans les régions à climat froid il se produira plus ces instructions : de condensat dans le système de ventilation.
  • Page 58: Installation De La Tuyauterie

    Vannes d'isolement  Ne bouchez pas la soupape de sûreté, et n'installez Rinnai recommande fortement l'installation de vannes aucun raccord réducteur ou autre restriction dans la d'isolement sur les lignes de l'eau chaude et froide. conduite de déversement. Elle doit permettre un Parce qu'ils permettent d'isoler le chauffe-eau de la drainage complet de la soupape et de la conduite.
  • Page 59 Tuyauterie recommandée pour installation de base Rinnai Water Heater Rinnai Equipment List Rinnai Water Heaters RIK-KIT (Optional) (3/4" Fittings Include: 2 Unions, 2 Ball Valves, 2 Drain Valves and 1 Pressure Relief Valve.) Connexion de gaz en 3/4 po (19 mm)
  • Page 60: Liste De Vérification Pour Tuyauterie

    Utilisez toujours des connecteurs approuvés pour chauffage de l'eau. Pression d'eau minimum est raccorder l'unité sur la conduite de gaz. Purgez de 50 psi. Rinnai recommande de 60-80 psi pour toujours la conduite de gaz de tous débris éventuels des performances optimales.
  • Page 61  Tout composé utilisé sur la jonction filetée du tuyau Table - gaz naturel de gaz doit être d'un type qui résiste à l'action du gaz Tuyau métallique annexe 40 propane ou naturel. La pression Inlet : moins de 2 psi (55 pouces W.C.) ...
  • Page 62: Reliez L'électricité

    Reliez l'électricité Ajustez à l'haute altitude Définissez les valeurs indiquées dans le tableau ci- AVERTISSEMENT dessous pour votre altitude commutateurs 2 et 3 N'utilisent pas une rallonge ou un adaptateur (SW1, commutateurs fauve). Le paramètre par brancher avec cet appareil. défaut pour l'appliance est 0-2000 ft (0-610 m) avec les commutateurs no 2 et 3 dans la position OFF.
  • Page 63: Installation De Le Contrôleur De Température

    Installation de le contrôleur de Montage du contrôleur température 1. Faire trois trous dans le mur, comme le montre. AVERTISSEMENT Outline of Remote Désactiver le pouvoir. Ne pas tenter de connecter les securing screw contrôleurs de température avec le pouvoir. Bien que le contrôleur est un dispositif de basse tension, il y a 1-21/32"...
  • Page 64: Liste De Vérification Finale

    Liste de vérification finale □ Le chauffage de l'eau n'est pas corrosifs composés □ Veiller à ce qu'une soupape est installée avec une dans l'air. cote qui dépasse l'entrée de BTU du modèle de □ L'approvisionnement en eau ne contient pas de chauffage de l'eau.
  • Page 65: Diagramme En Escalier

    Diagramme en escalier NEUTRE PHASE FUSIBLE 10 A CONTACT DE DÉTECTION DE GEL ANTI-FOUDRE RELAIS 2 ANTI-FOUDRE RELAIS 1 ALLUMAGE TERRE ALIMENTATION D'ÉNERGIE DE COMMUTATION 170 V CC 12,6 V 40 V CC 5 V CC 0-5 V CC DÉTECTEUR ÉLECTRO- D'ÉCOULEMENT VANNE À...
  • Page 66: Instructions D'utilisation

    V65e ..... REU-VC2025W-US Faits importants sur votre chauffe-eau Je vous remercie pour l'achat d'un chauffe-eau sans réservoir Rinnai. Pour le bon fonctionnement et la sécurité, il est important de suivre les instructions et de respecter les mesures de sécurité. Toutes les instructions et la garantie lire attentivement avant d'exploitation cette chauffe-eau. Gardez ce manuel en lieu sûr.
  • Page 67: Directives D'opérations Du Consommateur Pour Le Fonctionnement Sécuritaire De Votre Chauffe-Eau

    Directives d'opérations du consommateur pour le fonctionnement sécuritaire de votre chauffe-eau À LIRE AVANT LA MISE EN SERVICE POUR VOTRE SÉCURITÉ AVERTISSEMENT Si vous ne suivez pas exactement ces instructions, il peut en résulter un départ d'incendie ou une explosion, causant dégâts matériels, blessures corporelles ou même mort.
  • Page 68: Comment Utiliser Le Contrôleur De Température

    Comment utiliser le contrôleur de température Dimensions (pouces): 3.5 W x 4.75 H x 0.75 D Le contrôleur de MC-91-2 est le contrôleur de température standard qui est fourni avec l'appareil de chauffage de l'eau. Sur les modèles de l'intérieurs, elle est intégrée dans le panneau avant. Le contrôleur de MCC-91-2 est pour des applications hydroniques nécessitant des températures plus élevées.
  • Page 69: Comment Définir La Temperature

    Comment définir la température Cette chauffe eau nécessite un débit minimum à exploiter. Ce taux se trouvent sur la page de spécification dans ce manuel. Dans certains cas lorsque vous n'obtenez pas l'eau chaude ou si l'eau alterne entre le chaud et le froid, c'est en raison du débit de l'eau étant ci-dessous ou à...
  • Page 70 Arroser des températures plus de 125º F (52º C) peut causer des brûlures ou scalding sévère. Se référer à l'Alerte de Danger sur les températures d'eau. Rinnai ne fait pas, en tout cas, être responsable des dommages qui résultent de tel usage impropre ou tel mauvais usage.
  • Page 71: Entretien Requis

    Entretien requis L'appareil doit être inspecté chaque année par un technicien qualifié. Réparations et entretien doivent être effectuées par un technicien qualifié. Le technicien de service doit vérifier le bon fonctionnement après entre- tien. AVERTISSEMENT Pour vous protéger contre les préjudices, avant d'effectuer la maintenance : ...
  • Page 72 Nettoyez le filtre à eau Protection de gel Nettoyez le filtre à eau inlet en fermant les soupapes Assurez-vous que dans le cas de congélation météo d'isolement (fermeture) entrée froide et d'eau que le chauffe-eau et ses lignes de l'eau sont chaude.
  • Page 73: Flushing L'échangeur De Chaleur

    6. Placez le tuyau de drain (H3) et le tuyau (H2) à l'entrée de la pompe dans la solution de nettoyage. Rinnai 7. Ouvrez les deux valves de service (V1 et V2) sur l'eau chaude et de Water Heater conduites d'eau froides.
  • Page 74: Drainage Manuel Du Chauffe-Eau

    Drainage Manuel du chauffe-eau Pour éviter de burns, attendre jusqu'à ce que l'équipement se refroidit avant le AVERTISSEMENT drainage de l'eau. L'eau de l'appliance restera chaud après qu'il est éteint. Si le chauffe-eau ne va être utilisée pendant une période de temps au gel possible, il est recommandé que l'eau à l'intérieur du chauffe-eau être drainé.
  • Page 75: Garantie Du Consommateur

    Rinnai le remplacera par un produit comparable, à sa discrétion. Si un composant ou un produit retourné à Rinnai est trouvé sans défaut du aux matériaux ou à la main d'œuvre, ou qu'il est déterminé...
  • Page 76 Limitation sur les garanties Personne n'est autorisé à apporter toute autre Garantie limitée au nom de Rinnai pour ce produit. Sauf pour ce qui est expressément communiqué ici, il n'y a aucune autre Garantie limitée, explicite ou implicite, y compris sans y être limité les garanties de valeur marchande ou d'adéquation à...
  • Page 77 Value Series Manual...
  • Page 78 Value Series Manual...
  • Page 79 Value Series Manual...
  • Page 80 • Up to 0.96 Energy Factor (EF) Applications • Internal or External Installation ® • ENERGY STAR qualified models • Pair up with the Rinnai Air Handler for efficient home heating Direct Vent Furnaces • High Efficiency • Vent Terminal A Included • Cool-to-the-touch Cabinet •...