I N S TA L L E R ' S I N S TA L L AT I O N I N S T R U C T I O N S
(table assumes .3 inch pressure drop, specific gravity of .60)
Nominal
Iron Pipe
Size
Inches
10
20
3/4
278
190
1
520
350
1-1/4 1050
730
1-1/2 1600 1100
After determining the length of pipe required select the pipe size that will supply the
cubic feet per hour of gas required for the input rating of the Integrity V2532C.
The formula for figuring the cubic feet per hour required is:
*Gas input requirement is on the water heater data plate
*The heating value of the gas can be obtained from the local Natural Gas Utility
(table assumes 11 inches of water column pressure at the inlet, .5 inch drop)
Nominal
Iron Pipe
Size
Inches
10
1/2
275
3/4
567
1
1071
1-1/4 2205 1496 1212 1039
Model V2532FFUC
Gas Pipe Sizing Charts
Capacity Table for Natural Gas
Length of Pipe in Feet
30
40
50
152 130
115
285 245
215
590 500
440
890 760
670
Gas Input of Integrity V2532C(BTU/HR)
CFH =
Heating Value of Gas(BTU/FT
Capacity Table for LP Gas
BTUH of undiluted liquified petroleum gases
Length of Pipe in Feet
20
30
40
189
152
129
393
315
267
732
590
504
cubic feet / hour
60
70
80
105
96
90
195
180
170
400
370
350
610
560
530
50
60
70
237
217
196
448
409
378
913
834
771
2 7
90
100
125
84
79
72
160
150
130
320
305
275
490
460
410
)
3
80
90
100 125
185
173
162 146
346
322
307 275
724
677
630 567
150
175
200
64
59
55
120
110
100
250
225
210
380
350
320
150
252
511